SECTION 3 – USER INTERFACE
PAGE 3-4 REV. 0 2014-MAY-02
DISPLAY MODULE FRONT PANEL INDICATORS
Power LED (See Figure 3-3)
• Internal Power status – Power lEd pulses GREEn 1 x 3
seconds during normal operation
• External Power/dual Power status - Power lEd illuminates
GREEn and remains steady-on during normal operation
• Power Fault Conditions
o Independent Internal Power Fault status - Amber Power
LED and sounder pulse 1 x 10 seconds indicating power
from the internal power source dropped below acceptable
level causing a fault condition.
o Independent External Power Fault status – amber Power
LED and sounder pulse 1 x 10 seconds indicating power
from the external power source dropped below acceptable
level causing a fault condition.
o Internal/External Dual Power Fault status - Amber Power
LED pulses 1 x 3 seconds indicating power from the exter-
nal power source dropped below acceptable level causing
a fault condition and system is operating on internal power
supply (sounder does not operate to conserve power).
o Internal Battery life Fault - amber Power lEd and
sounder pulse 1 x 10 seconds indicating power from the
internal power source dropped below acceptable level
causing a fault condition.
o Fault conditions will continue pulsing aMBER as long as
fault exists or until system powers down.
Release Circuit LED (See Figure3-3)
• Pulses aMBER 1 x 10 seconds (sounder matches pulse
rate) during a fault condition
• Returns to normal (no indication) when fault is cleared
Discharge LED (See Figure 3-3)
this lEd is only active when Pressure switch Feedback is
programmed.
• Illuminates REd steady-on when pressure switch activates
for the remainder of Release Activated period (see Table
3-1)
• Pulses REd 1 x 10 seconds in post release activated (see
Table 3-1)
• Controlled by an external pressure switch and provides indi
-
cation of rising pressure in the expellant gas line
FIGURE 3-3
DISPLAY MODULE FRONT PANEL
009290
Detection Circuit #1 LED (See Figure 3-3)
• Pulses REd in an alarm condition (see table 3-1)
• Pulses aMBER 1 x 10 seconds (sounder matches pulse
rate) during a fault condition
• Returns to normal (no indication) when fault or alarm condi
-
tion is cleared
Detection Circuit #2 LED (See Figure 3-3)
• Pulses REd in an alarm condition (see table 3-1)
• Pulses aMBER 1 x 10 seconds (sounder matches pulse
rate) during a fault condition
• Returns to normal (no indication) when fault or alarm condi
-
tion is cleared
Isolate LED (See Figure 3-3)
• Pulses aMBER 2 x 30 seconds to indicate the system is in
Isolate Mode
• use Isolate Mode when performing maintenance on the
vehicle/equipment to inhibit automatic release of the fire
suppression system
CHECKFIRE 210
Detection and Actuation System
RELEASE
CIRCuIt lEd –
aMBER
DETECTIon
CIRCuIt #1 lEd –
aMBER oR REd
IsolatE lEd –
aMBER
DETECTIon
CIRCuIt #2 lEd –
aMBER oR REd
DISCHARGE
lEd – REd
sHutdoWn lEd – REd
PowER
lEd –
GREEn
oR
aMBER
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...