SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
PAGE 6-8 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
External Power Circuit – Supervision Test (Dual Power)
Disconnect the external power circuit connection at the
CHECKFIRE 210 ICM Power Circuit receptacle.
1. Power LED pulses AMBER 1 x 3 seconds.
2. Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
After reset, Power LED pulses GREEN 1 x 3 seconds
confirming external power loss and operation on internal
power.
3. Reconnect external power circuit at the ICM. The
CHECKFIRE 210 Display Module Power LED is GREEN
steady-on.
009290
POwER
SUPERVISION
(REMOVE POwER
CABLE)
AMBER LED PULSES
1 X 3 SECONDS
009290
POWER
SUPERVISION
AFTER RESET
WITHOUT
EXTERNAL POWER
GREEN LED
PULSES
1 X 3 SECONDS
009290
RECONNECT
EXTERNAL POWER
SYSTEM
RETURNS TO
NORMAL STATUS
POWER LED IS
GREEN
STEADY-ON
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...