920.1020.12
21
STEP 8:
WIRING CONNECTIONS
(wiring diagrams are located in the Appendix)
I/O BOARD CONNECTIONS
Position
Function
Description
TER
M
IN
A
L
STR
IP
J
5
1
Electric Lock
Relay
Common
2
Electric Lock
Relay
N.O. Dry contact – Contact closes upon activation. May be used for fail-secure locks by
routing 1 leg of power though the relay. Relay is triggered by activation inputs 10, 11, or
16. Relay remains energized until door is fully closed again.
3
Electric Lock
Relay
N.C. Dry Contact - Contact opens upon activation. May be used for fail-safe locks by
routing 1 leg of power though the relay. Relay is triggered by activation inputs 10, 11, or
16. Relay remains energized until door is fully closed again.
4
Door Status -
Closed
N.O. Contact is closed when door is closed. The contact opens as soon as the door
opens.
5
Door Status –
Common
Common contact for door status
6
Door Status -
Open
N.C. – Contact is closed when door is open. The contact opens as soon as the door starts
to close. This input can be used for motor connection at lockout relay when power is
looped through, thus switching power on when door is open.
TER
M
IN
A
L
STR
IP
J
4
7
GND
Common GND
8
GND
Common GND
9
+ 24 VDC
.5A Max. Current
10
Internal
Activation
Requires N.O. Contact between input 10 & COM. Remains capable to activate when dip
switch 3 is ON AND On-Off switch is OFF.
11
External
Activation
Requires N.O. Contact between input 11 & COM.
12
Emergency
Closing
Requires N.C. contact between 12 & COM. Upon open contact, door closes and overrides
all other inputs. Remains jumpered if input is not used.
13
Secondary
Activation
Requires N.C. contact between 13 & COM. Disabled in full closed position.
14
“Stall” Safety
Requires N.C. contact between 14 & COM. Upon open contact, (Dip 6 OFF) during
opening, door stops, then resumes at reduced speed when input is released.
15
Not Used
Not Used
16
Alarm Input
N.O. contact, when closed causes door closing. All inputs inhibited during closed contact
(not available on all software versions)
17
Overhead
Presence
Sensor Input
Requires N.O. contact between 14 & +24 VDC (input 9). When input is closed it causes an
open door to stay open and a closed door to stay closed. Works in conjunction with dip
switch #6.
18
GND
Common GND
19
GND
Common GND
20
Aux Relay
Auxiliary Relay NOTE: Relay is triggered by input 14
21
Aux Relay
Auxiliary Relay N.O.
22
Aux Relay
Auxiliary Relay N.C.
23
Alarm Output -
Common
Common
24
Alarm Output
N.O. output is closed upon closed contact from fire alarm. LED 2 also illuminates.
25
+ 24 VDC
.5A max.
26
GND
Common GND
Inputs 27 & 28 not used
Содержание SW10
Страница 11: ...920 1020 12 11 PUSH ARM ...
Страница 27: ...920 1020 12 27 SETUP BUTTON FLASHING RED LED ...
Страница 33: ...920 1020 12 33 APPENDIX WIRING DIAGRAMS SIMULTANEOUS PAIRS ...
Страница 35: ...920 1020 12 35 APPENDIX WIRING DIAGRAMS ELECTRIC LOCK APPLICATION ...
Страница 36: ...920 1020 12 36 APPENDIX WIRING DIAGRAMS SW10 PAIR WITH BEA PARALLAX SYSTEM ...
Страница 37: ...920 1020 12 37 APPENDIX WIRING DIAGRAMS SW10 Single Pair WIth BEA LZR Microscan Sensors ...
Страница 38: ...920 1020 12 38 APPENDIX WIRING DIAGRAMS SW10 Single With Push Plates Torpedo Sensors For Secondary Activation ...
Страница 42: ...920 1020 12 42 APPENDIX TUCKER LOGO ...