![Trox Technik X-CUBE Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/trox-technik/x-cube/x-cube_transport-and-installation-manual_1172434056.webp)
Adjusting inspection access doors
Personnel:
HVAC technician
Protective equipment:
Industrial safety helmet
Protective clothing
Protective gloves
Safety shoes
Fig. 63: Adjusting the door
1.
Remove the hinge covers (Fig. 63/1) from the
Adjusting the door horizontally
2.
Loosen the screws of all hinge brackets (Fig. 63/2)
of a door.
3.
Adjust the door horizontally (Fig. 63/5).
4.
Tighten the screws of the hinge brackets
Adjusting the door vertically
5.
Loosen the screws of all hinge blocks (Fig. 63/3)
on a door.
6.
Adjust the door vertically (Fig. 63/4).
7.
Tighten the screws of the hinge blocks (Fig. 63/3).
Adjusting the staple
Leaking inspection access doors
If an inspection access door leaks, you can easily
adjust the staple.
Fig. 64: Staple cover
8.
Remove the staple cover (Fig. 64/1).
Fig. 65: Staple
9.
Loosen the locking screws (Fig. 65/2) (SW3).
10.
Adjust the staple by turning the setting screws
11.
Tighten the locking screws (Fig. 65/2) and replace
the staple cover (Fig. 64/1).
ð
The inspection access doors have been
adjusted.
6.3.2
Centrifugal fan
Operating point
The control system calculates the operating point and
sets the default setpoint value for the fan.
Initial commissioning
Setting up and adjusting AHU casing units > Centrifugal fan
Air handling unit X-CUBE
56