Compressed seals will recover fully to their
original state about 60 minutes after the trans-
port protection devices have been removed.
Check that the seals are complete and intact and
that they seal properly.
Setting up AHU casing units
Slide plates (Fig. 13/3) considerably simplify the
process of positioning the AHU casing units (Fig. 13/1)
on a surface with a high friction coefficient, such as
rubber or elastomer sheets (Fig. 13/4).
The arrangement of the AHU casing units is given in
the order-specific approval drawing.
Fig. 13: Unit arrangement with anti vibration elements
1.
Position the slide plates (Fig. 13/3, by others)
under the base frames (Fig. 13/2) of the AHU
2.
Move the AHU casing units as close together as
possible.
Fig. 14: Aligning AHU casing units
3.
Align the AHU casing units such that they are
flush with one another (Fig. 14/1).
AHU units with X-CUBE Control:
Before you push the AHU casing units together,
insert the internal cables of each unit into the cable
ducts of the next casing unit; for more information
see
Chapter 5.6 ‘Wiring’ on page 45.
Setting up units with a base frame
Fig. 15: Attaching a ratchet strap
1.
Attach a ratchet strap to the base frames of two
AHU casing units (Fig. 15).
2.
Tighten the ratchet strap.
ð
The AHU casing units come closer together as
you tighten the strap around the base frames.
Alternatively:
Setting up units without a base frame
1.
Attach a ratchet strap to the bottom or top areas of
two AHU casing units.
2.
Tighten the ratchet strap.
ð
The AHU casing units come closer together as
you tighten the strap.
Setup and assembly
Setting up and assembling the air handling unit > Setting up the AHU or AHU casing units
Air handling unit X-CUBE