Registration of MCI modules
If compatible equipment is connected to the control panel MCI data bus to be recognised by the
control panel and made a communication with it, this equipment shall be registered manually.
Regarding registering, see 6.15 “Transmission module registration”.
5.1.4
Alarm system operation testing
Upon completion of the alarm system installation, it shall be tested for correct operation.
5.1.4.1
Walk-test function
Operation of sensors and siren can be tested by carrying out a Walk-test function by using Trikdis Protegus
SK130 or SK232 keyboards. The following shall be done:
1.
Press the button [OK].
2.
Enter installer (Installer) code.
3.
Press the button [TRB].
a.
The buttons STAY and ARM shall start flashing and the alarm shall switch over to the testing
mode.
b.
Due to change of the zone statuses, the sirens and keyboard buzzer shall beep by informing
about the zone operation.
c.
If during testing the sensor fuse has been tampered or the protection mode is on, the testing
mode shall terminate automatically.
To switch off the mode, repeat the procedure as switching it on.
5.1.4.2
Testing of report transmission system
If GRPS network parameters are correctly set with the Central Monitoring Station addresses, upon switching on
the power supply to the system the following shall take place:
a)
A report E305 System Reset shall be sent.
b)
If compatible, but unregistered, modules are connected to the control panel YEL/GRN data bus, there
shall be sent as many reports R333 Expansion Module Restore as there are to be newly registered
modules.
c)
If in the control panel, communication control parameters the communication verification signal PING is
on, a report E760 (Control panel PING signal) shall be sent. When the IP receiver gets the report, it shall
start automatic control of the communication channel with the control panel.
Also, it is possible to manually formulate the communication testing report E602 (Periodical Test). It is
recommended to inform in advance the security service about the testing.
Testing of the report transmission by using Trikdis Protegus SK130 or SK232 keyboards shall be as follows:
1.
Press the button [OK].
2.
Enter installer (Installer) code.
3.
Press the button [MEM].