RT-PRC006-EN
60
Performance
Data
(4 Ton)
High Efficiency
Table PD-60 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1280
614
0.22
675
0.26
733
0.31
787
0.37
834
0.42
878
0.48
919
0.53
959
0.59
997
0.65
1034
0.71
1440
676
0.30
731
0.34
784
0.39
835
0.46
883
0.52
925
0.58
965
0.64
1003
0.70
1039
0.76
1075
0.83
1600
739
0.40
789
0.45
838
0.50
885
0.56
931
0.63
973
0.70
1012
0.77
1049
0.84
1085
0.91
1118
0.97
1760
803
0.51
850
0.57
894
0.63
938
0.69
981
0.76
1021
0.83
1061
0.92
1097
0.99
1131
1.07
1164
1.14
1920
867
0.65
911
0.72
952
0.78
993
0.84
1033
0.91
1071
0.99
1110
1.07
1145
1.16
1180
1.25
1213
1.33
Table PD-60 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1280
1069
0.77
1104
0.83
1138
0.90
1170
0.97
1203
1.04
1440
1109
0.89
1141
0.96
1175
1.03
1205
1.10
1236
1.17
1600
1151
1.04
1183
1.11
1215
1.19
1246
1.26
1275
1.33
1760
1197
1.21
1227
1.29
1258
1.36
1287
1.44
—
—
1920
1243
1.41
1274
1.49
—
—
—
—
—
—
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to
other options/accessoriesdue to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be
necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of
our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.
Table PD-61 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1280
627
0.23
688
0.27
745
0.32
797
0.38
844
0.43
887
0.49
928
0.54
967
0.60
1006
0.66
1042
0.72
1440
691
0.31
746
0.36
798
0.41
848
0.47
894
0.54
936
0.60
975
0.66
1012
0.72
1049
0.78
1085
0.85
1600
756
0.41
806
0.47
854
0.52
901
0.58
945
0.66
987
0.73
1025
0.79
1061
0.86
1096
0.93
1129
1.00
1760
822
0.54
868
0.60
912
0.65
955
0.71
997
0.79
1038
0.87
1076
0.95
1111
1.02
1145
1.10
1178
1.17
1920
889
0.69
931
0.75
972
0.81
1012
0.88
1051
0.95
1090
1.03
1127
1.11
1162
1.20
1196
1.29
1228
1.37
Table PD-61 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1280
1077
0.78
1112
0.85
1145
0.91
1178
0.98
1210
1.05
1440
1118
0.91
1150
0.98
1183
1.05
1214
1.12
1244
1.19
1600
1162
1.06
1193
1.13
1225
1.21
1255
1.28
1285
1.36
1760
1208
1.24
1239
1.32
1268
1.39
1297
1.47
—
—
1920
1258
1.45
—
—
—
—
—
—
—
—
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to
other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be
necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of
our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.