RT-PRC006-EN
40
Performance
Data
(3 Ton)
Standard Efficiency
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-23 — Belt Drive Evaporator Fan Performance — 3 Ton — YSC036A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
960
563
0.13
639
0.18
707
0.23
766
0.28
817
0.33
864
0.39
908
0.44
947
0.49
985
0.55
1020
0.60
1080
611
0.18
685
0.23
748
0.28
806
0.34
858
0.39
905
0.45
947
0.51
988
0.58
1026
0.64
1061
0.70
1200
660
0.23
732
0.29
792
0.34
847
0.40
899
0.46
945
0.53
989
0.59
1029
0.66
1066
0.73
1102
0.80
1320
711
0.29
781
0.36
838
0.42
890
0.48
940
0.55
986
0.61
1029
0.68
1070
0.76
1106
0.83
1142
0.90
1440
762
0.37
829
0.44
885
0.51
935
0.57
983
0.64
1028
0.71
1070
0.79
1111
0.86
1148
0.94
1183
1.02
1-HP Standard Motor & Field SuppliedHigh Static Drive (2)
Table PD-23 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard
Motor & Drive
960
1056
0.66
1090
0.71
1123
0.78
1156
0.84
1188
0.90
1080
1096
0.76
1128
0.82
1159
0.88
1190
0.94
1220
1.00
1200
1135
0.87
1168
0.93
1199
1.00
1229
1.07
1259
1.13
1320
1177
0.98
1209
1.06
1241
1.14
1270
1.21
1299
1.28
1440
1217
1.10
1250
1.18
1281
1.27
1311
1.35
1339
1.43
1-HP Standard Motor & Field
Supplied High Static Drive (2)
Table PD-22 — Belt Drive Evaporator Fan Performance — 3 Ton — YSC036A3,A4,AW*L, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
960
552
0.13
631
0.17
699
0.22
759
0.27
811
0.33
858
0.38
902
0.44
943
0.49
980
0.54
1017
0.60
1080
598
0.17
675
0.22
739
0.27
798
0.33
850
0.38
898
0.44
941
0.50
982
0.57
1020
0.63
1056
0.69
1200
645
0.22
720
0.28
781
0.33
837
0.39
889
0.45
937
0.51
981
0.58
1021
0.65
1059
0.72
1095
0.79
1320
693
0.28
766
0.34
825
0.40
879
0.47
929
0.53
976
0.60
1020
0.67
1061
0.74
1099
0.81
1135
0.89
1440
743
0.35
811
0.42
871
0.49
922
0.55
970
0.62
1016
0.69
1059
0.77
1099
0.84
1138
0.92
1174
1.00
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-22 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
960
1052
0.65
1086
0.71
1120
0.77
1152
0.83
1185
0.90
1080
1090
0.75
1123
0.81
1154
0.87
1185
0.93
1215
0.99
1200
1130
0.86
1162
0.92
1193
0.99
1224
1.05
1253
1.12
1320
1169
0.96
1203
1.04
1233
1.12
1263
1.19
1292
1.26
1440
1208
1.08
1241
1.16
1273
1.25
1303
1.33
1332
1.41
1-HP Standard Motor &