RT-PRC006-EN
52
(8½ Ton)
Standard Efficiency
Performance
Data
Table PD-46 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
2-HP Standard Motor & Drive
Low Static Drive (1
)
2720
—
—
—
—
608
0.59
649
0.70
689
0.82
728
0.94
764
1.06
798
1.19
829
1.33
859
1.46
3060
—
—
615
0.65
654
0.75
692
0.87
728
0.99
764
1.13
799
1.26
833
1.39
864
1.53
894
1.68
3400
625
0.72
665
0.83
702
0.95
736
1.06
770
1.19
804
1.34
836
1.49
868
1.63
899
1.78
928
1.93
3740
681
0.93
716
1.05
752
1.18
784
1.31
815
1.44
846
1.58
876
1.74
906
1.90
935
2.06
963
2.22
4080
737
1.19
769
1.31
802
1.45
833
1.60
862
1.73
891
1.87
919
2.03
947
2.20
974
2.37
1001
2.55
Table PD-46 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
3-HP Oversized Motor & Drive
2720
888
1.61
916
1.76
943
1.91
970
2.07
996
2.22
1021
2.37
1046
2.53
1071
2.69
1096
2.86
1119
3.02
3060
922
1.82
949
1.98
976
2.14
1001
2.31
1026
2.47
1051
2.65
1074
2.81
1098
2.99
1120
3.16
1144
3.34
3400
957
2.08
984
2.24
1011
2.41
1035
2.58
1060
2.75
1083
2.93
1106
3.11
1128
3.29
—
—
—
—
3740
992
2.39
1018
2.55
1045
2.72
1070
2.90
1095
3.08
1117
3.25
1140
3.44
—
—
—
—
—
—
4080
1028
2.73
1053
2.90
1079
3.07
1104
3.26
1128
3.44
—
—
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-47 — Belt Drive Evaporator Fan Performance — 8½ Ton — YSC102A3,A4,AW, AK *H— High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
2-HP Standard Motor & Drive
Low Static Drive (1
)
2720
—
—
—
—
619
0.62
661
0.74
700
0.85
738
0.97
773
1.09
807
1.23
838
1.36
868
1.51
3060
586
0.58
629
0.68
667
0.79
705
0.91
741
1.04
776
1.17
810
1.30
843
1.44
874
1.58
904
1.72
3400
642
0.76
681
0.88
717
1.00
751
1.12
785
1.25
817
1.40
849
1.55
881
1.69
911
1.84
940
1.99
3740
698
0.99
735
1.12
769
1.25
800
1.37
831
1.51
862
1.66
892
1.82
920
1.98
950
2.14
977
2.30
4080
756
1.26
789
1.40
821
1.54
851
1.68
879
1.82
908
1.97
936
2.13
964
2.30
991
2.48
1017
2.66
Table PD-47 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
3-HP Oversized Motor & Drive
2720
896
1.65
923
1.80
950
1.95
977
2.11
1003
2.26
1029
2.42
1053
2.57
1078
2.74
1102
2.90
1124
3.06
3060
932
1.88
959
2.04
985
2.20
1010
2.36
1034
2.53
1058
2.70
1082
2.87
1105
3.05
1129
3.22
1151
3.39
3400
969
2.15
996
2.31
1020
2.48
1045
2.65
1070
2.83
1093
3.00
1116
3.19
1138
3.37
—
—
—
—
3740
1005
2.47
1032
2.64
1058
2.81
1083
2.99
1106
3.16
1129
3.35
—
—
—
—
—
—
—
—
4080
1044
2.83
1069
3.01
1095
3.19
1119
3.37
—
—
—
—
—
—
—
—
—
—
—
—