RT-PRC006-EN
56
(3 - 5 Tons)
High Efficiency
Performance
Data
Table PD-54— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton
YHC036A**L,M, YHC048A**L,M, YHC060A**L,M
— Low and Medium Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)
1
Standard Motor
Oversized Motor
2
Unit
High Speed
Low Speed
High Speed
Low Speed
Tons Model No.
CFM
ESP
BHP
ESP
BHP
ESP
BHP
ESP
BHP
960
0.74
0.36
0.56
0.28
0.89
0.38
0.82
0.35
1020
0.69
0.37
0.49
0.28
0.85
0.39
0.77
0.36
1080
0.65
0.38
0.44
0.29
0.82
0.41
0.74
0.38
1140
0.61
0.39
0.37
0.29
0.77
0.43
0.69
0.40
3
YHC036A**L,M
1200
0.55
0.40
0.29
0.30
0.74
0.44
0.65
0.41
Horizontal Airflow
1260
0.51
0.41
0.19
0.30
0.70
0.45
0.61
0.42
1320
0.46
0.42
0.10
0.31
0.67
0.47
0.57
0.44
1380
0.41
0.43
0.00
0.31
0.64
0.48
0.52
0.45
1440
0.34
0.44
—
—
0.57
0.51
0.45
0.48
1280
0.85
0.53
0.74
0.47
1.11
0.67
0.90
0.56
1360
0.78
0.54
0.66
0.47
1.06
0.68
0.85
0.58
1440
0.71
0.54
0.60
0.48
1.01
0.70
0.80
0.60
1520
0.64
0.55
0.51
0.48
0.96
0.73
0.72
0.63
4
YHC048A**L,M
1600
0.55
0.55
0.39
0.49
0.89
0.75
0.63
0.64
Horizontal Airflow
1680
0.46
0.56
0.27
0.49
0.84
0.78
0.54
0.66
1760
0.37
0.56
0.12
0.50
0.79
0.82
0.37
0.68
1840
0.26
0.57
0.00
0.50
0.70
0.83
0.24
0.70
1920
0.16
0.57
—
—
0.62
0.85
0.13
0.73
1600
0.99
0.78
0.89
0.64
1.32
0.90
1.18
0.85
1700
0.92
0.80
0.76
0.65
1.24
0.94
1.08
0.89
1800
0.87
0.85
0.65
0.65
1.16
0.98
0.97
0.91
1900
0.77
0.88
0.56
0.65
1.15
1.02
0.87
0.94
5
YHC060A**L,M
2000
0.69
0.90
0.40
0.66
0.98
1.05
0.76
0.95
Horizontal Airflow
2100
0.59
0.93
0.25
0.66
0.89
1.10
0.63
0.96
2200
0.46
0.94
0.10
0.67
0.78
1.12
0.42
0.96
2300
0.37
0.95
—
—
0.68
1.17
0.18
0.97
2400
0.26
0.97
—
—
0.55
1.20
—
—
960
0.74
0.36
0.56
0.28
0.89
0.38
0.82
0.35
1020
0.69
0.37
0.49
0.28
0.85
0.39
0.77
0.36
1080
0.65
0.38
0.44
0.29
0.82
0.41
0.74
0.38
1140
0.61
0.39
0.37
0.29
0.77
0.43
0.69
0.40
3
YHC036A**L,M
1200
0.55
0.40
0.29
0.30
0.74
0.44
0.65
0.41
Downflow Airflow
1260
0.51
0.41
0.19
0.30
0.70
0.45
0.61
0.42
1320
0.46
0.42
0.10
0.31
0.67
0.47
0.57
0.44
1380
0.41
0.43
0.00
0.31
0.64
0.48
0.52
0.45
1440
0.34
0.44
—
—
0.57
0.51
0.45
0.48
1280
0.90
0.53
0.79
0.47
1.16
0.67
0.95
0.56
1360
0.83
0.54
0.71
0.47
1.11
0.68
0.90
0.58
1440
0.76
0.54
0.65
0.48
1.06
0.70
0.85
0.60
1520
0.69
0.55
0.56
0.48
1.01
0.73
0.77
0.63
4
YHC048A**L,M
1600
0.60
0.55
0.44
0.49
0.94
0.75
0.68
0.64
Downflow Airflow
1680
0.51
0.56
0.32
0.49
0.89
0.78
0.59
0.66
1760
0.42
0.56
0.17
0.50
0.84
0.82
0.42
0.68
1840
0.31
0.57
0.05
0.50
0.75
0.83
0.29
0.70
1920
0.21
0.57
–
—
0.67
0.85
—
—
1600
1.04
0.78
0.94
0.64
1.37
0.90
1.23
0.85
1700
0.97
0.80
0.81
0.65
1.29
0.94
1.13
0.89
1800
0.92
0.85
0.70
0.65
1.21
0.98
1.02
0.91
1900
0.82
0.88
0.61
0.65
1.20
1.02
0.92
0.94
5
YHC060A**L,M
2000
0.74
0.90
0.45
0.66
1.03
1.05
0.81
0.95
Downflow Airflow
2100
0.64
0.93
0.30
0.66
0.94
1.10
0.68
0.96
2200
0.51
0.94
0.15
0.67
0.83
1.12
0.47
0.96
2300
0.42
0.95
—
—
0.73
1.17
0.23
0.97
2400
0.31
0.97
—
—
0.60
1.20
—
—
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
Notes:
1. Data includes pressure drop due to wet coil and filters.