Table PD-78 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1
)
2720
—
—
590
0.55
633
0.66
674
0.77
713
0.89
750
1.01
786
1.14
818
1.28
850
1.42
879
1.56
3060
602
0.62
643
0.72
682
0.83
719
0.96
756
1.09
791
1.23
825
1.36
857
1.50
889
1.65
917
1.80
3400
660
0.82
698
0.94
733
1.05
767
1.18
801
1.32
834
1.48
866
1.62
897
1.77
927
1.92
956
2.08
3740
718
1.06
754
1.19
787
1.32
818
1.45
849
1.60
880
1.76
910
1.92
939
2.08
968
2.24
996
2.41
4080
777
1.35
811
1.49
841
1.63
870
1.77
899
1.92
928
2.08
956
2.26
983
2.43
1011
2.61
1037
2.79
2-HP Standard Motor & Drive
3-HP Oversized Motor & Drive
Table PD-78 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
2720
907
1.71
934
1.86
960
2.01
987
2.17
1014
2.33
1039
2.48
1063
2.64
1088
2.81
1112
2.97
1134
3.13
3060
945
1.95
971
2.11
997
2.28
1022
2.45
1047
2.62
1070
2.79
1094
2.96
1117
3.14
1141
3.31
—
—
3400
985
2.24
1010
2.40
1036
2.58
1060
2.76
1084
2.93
1106
3.11
1130
3.31
—
—
—
—
—
—
3740
1023
2.58
1049
2.75
1075
2.93
1099
3.11
1122
3.29
—
—
—
—
—
—
—
—
—
—
4080
1063
2.96
1089
3.15
1114
3.34
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-79 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L— Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1
)
2720
622
0.62
669
0.73
711
0.84
760
0.97
807
1.12
849
1.26
884
1.38
915
1.50
944
1.62
972
1.74
3060
688
0.85
732
0.97
770
1.09
809
1.22
853
1.38
895
1.54
934
1.70
968
1.85
998
1.99
1026
2.13
3400
756
1.14
795
1.27
832
1.40
866
1.54
901
1.69
941
1.86
979
2.04
1015
2.22
1049
2.40
1079
2.56
3740
824
1.49
859
1.62
895
1.78
926
1.92
957
2.07
990
2.24
1025
2.42
1061
2.62
1095
2.82
1127
3.02
4080
893
1.90
925
2.05
958
2.21
988
2.37
1017
2.53
1046
2.70
1075
2.88
1108
3.08
1140
3.29
—
—
2-HP Standard Motor & Drive
3-HP Oversized Motor & Drive
Table PD-79 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
2720
998
1.86
1024
1.98
1047
2.10
1071
2.22
1094
2.33
1115
2.45
1138
2.57
1159
2.69
1181
2.82
1201
2.94
3060
1053
2.26
1078
2.39
1102
2.53
1125
2.66
1146
2.79
1169
2.93
1190
3.06
1210
3.19
1230
3.32
1250
3.45
3400
1106
2.71
1131
2.86
1156
3.02
1179
3.16
1201
3.31
1223
3.45
—
—
—
—
—
—
—
—
3740
1158
3.21
1185
3.39
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
4080
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.