49
RT-PRC006-EN
(7½ Ton)
Standard Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-40 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW, AK *L — Low Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
2-HP Standard Motor & Drive
Low Static Drive (1
)
2400
—
—
—
—
676
0.59
726
0.67
773
0.77
815
0.85
854
0.94
891
1.03
928
1.12
963
1.22
2700
—
—
682
0.68
727
0.76
770
0.85
814
0.95
856
1.06
895
1.16
931
1.25
965
1.35
998
1.45
3000
693
0.79
738
0.89
780
0.97
819
1.07
858
1.18
898
1.29
936
1.40
972
1.52
1006
1.63
1038
1.73
3300
753
1.03
795
1.14
834
1.23
871
1.33
906
1.45
942
1.56
978
1.69
1014
1.81
1048
1.94
1080
2.06
3600
814
1.31
853
1.44
890
1.55
925
1.65
958
1.76
991
1.88
1023
2.01
1057
2.14
1088
2.28
1121
2.41
Table PD-40 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2- HP Standard Motor & Drive
2-HP Standard Motor & High Static DriveKit (or 3-HP Oversized Motor & Drive)
2400
996
1.32
1028
1.42
1061
1.52
1092
1.63
1122
1.73
1151
1.83
1180
1.93
1207
2.03
1235
2.14
1261
2.24
2700
1031
1.56
1062
1.66
1093
1.78
1123
1.89
1153
2.00
1181
2.12
1209
2.23
1236
2.35
1262
2.47
1288
2.58
3000
1070
1.85
1099
1.95
1128
2.07
1158
2.19
1185
2.31
1213
2.43
1240
2.55
1267
2.68
1293
2.81
1319
2.94
3300
1110
2.18
1139
2.29
1167
2.42
1195
2.54
1222
2.66
1248
2.79
1274
2.92
1301
3.05
1325
3.18
1351
3.33
3600
1151
2.55
1181
2.68
1208
2.81
1236
2.95
1261
3.07
1287
3.21
1311
3.33
—
—
—
—
—
—
3-HP Oversized Motor & Drive
3-HP Oversized Motor
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-41 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & High Static Drive Kit
2-HP Standard Motor & Drive
(or 3-HP Oversized Motor & Drive)
2400
1019
1.39
1051
1.49
1083
1.60
1113
1.70
1141
1.80
1171
1.90
1199
2.01
1225
2.10
1252
2.20
1278
2.31
2700
1058
1.65
1089
1.76
1120
1.87
1149
1.99
1178
2.10
1205
2.21
1232
2.33
1259
2.45
1284
2.56
1310
2.68
3000
1101
1.96
1131
2.08
1160
2.20
1187
2.31
1215
2.44
1243
2.57
1269
2.69
1295
2.82
1321
2.95
1346
3.08
3300
1147
2.33
1176
2.45
1204
2.58
1230
2.70
1256
2.82
1282
2.96
1308
3.09
1333
3.23
1358
3.36
—
—
3600
1196
2.75
1223
2.88
1250
3.02
1276
3.15
1301
3.28
1325
3.41
—
—
—
—
—
—
—
—
3-HP Oversized Motor & Drive
Table PD-41 — Belt Drive Evaporator Fan Performance — 7½ Ton — YSC090,092A3,A4,AW *M— Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied Low Static Drive (1
)
2-HP Standard Motor & Drive
2400
—
—
662
0.56
711
0.65
759
0.74
802
0.83
842
0.91
879
1.00
916
1.09
951
1.19
986
1.29
2700
676
0.67
721
0.75
764
0.84
809
0.94
851
1.04
891
1.14
927
1.24
961
1.34
994
1.44
1027
1.54
3000
741
0.89
783
0.98
822
1.08
861
1.19
901
1.30
939
1.41
975
1.52
1009
1.64
1041
1.74
1071
1.85
3300
807
1.17
846
1.26
882
1.37
917
1.48
953
1.60
989
1.72
1024
1.85
1058
1.97
1089
2.09
1119
2.21
3600
874
1.50
910
1.60
944
1.71
976
1.83
1008
1.95
1041
2.08
1074
2.22
1107
2.35
1138
2.49
1168
2.62
3-HP Oversized Motor
& Drive
2-HP Standard Motor & High Static Drive (or 3-HP Oversized Motor)