63
RT-PRC006-EN
Performance
Data
(5 Ton)
High Efficiency
Table PD-66 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
1239
1.19
1272
1.28
1304
1.37
1336
1.46
1800
1299
1.43
—
—
—
—
—
—
2000
—
—
—
—
—
—
—
—
2200
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
Table PD-66 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
775
0.42
837
0.50
898
0.57
952
0.65
1000
0.72
1044
0.79
1086
0.87
1127
0.95
1166
1.03
1203
1.11
1800
856
0.58
912
0.66
967
0.74
1020
0.83
1069
0.91
1112
1.00
1152
1.08
1189
1.16
1227
1.25
1263
1.34
2000
939
0.77
990
0.86
1040
0.96
1089
1.05
1136
1.14
1180
1.24
1219
1.33
1256
1.42
1292
1.50
—
—
2200
1023
1.01
1070
1.11
1115
1.21
1160
1.31
1205
1.41
—
—
—
—
—
—
—
—
—
—
2400
1108
1.29
1151
1.39
1193
1.50
—
—
—
—
—
—
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-67 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
1251
1.22
1283
1.31
1315
1.40
1345
1.49
1800
1313
1.47
—
—
—
—
—
—
2000
—
—
—
—
—
—
—
—
2200
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-67 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
796
0.45
858
0.52
917
0.60
969
0.67
1015
0.75
1059
0.82
1100
0.90
1141
0.98
1178
1.06
1216
1.14
1800
881
0.61
935
0.70
991
0.78
1042
0.87
1087
0.95
1129
1.03
1168
1.12
1206
1.20
1244
1.29
1279
1.38
2000
967
0.82
1016
0.91
1066
1.01
1115
1.10
1160
1.19
1201
1.28
1239
1.38
1275
1.47
—
—
—
—
2200
1054
1.07
1099
1.17
1144
1.27
1189
1.38
1233
1.48
—
—
—
—
—
—
—
—
—
—
2400
1141
1.37
1183
1.48
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1-HP Standard Motor &
Field Supplied Low Static Drive (1)
1-HP Standard Motor &
Field Supplied High Static Drive (1
)