RT-PRC006-EN
18
(5 - 6 Tons)
Standard Efficiency
Table GD-2 — Continued
5 Ton Convertible
6 Ton Convertible
YSC060A1
YSC060A3, A4, AW, AK
YSC072A3, A4, AW, AK
Belt Drive Indoor Fan
- Type
—
FC Centrifugal
FC Centrifugal
No. Used/Diameter (in.)
—
1/11 x 11
1/12 x 12
Drive Type/No. Speeds
—
Belt/Variable Sheave
Belt/Variable Sheave
No. Motors
—
1
1
Motor HP (Standard/Oversized)
—
1.00/—
1.00/2.00
17
Motor RPM (Standard/Oversized)
—
1,750/ —
1,750/1,750
Motor Frame Size (Standard/Oversized)
—
48/—
56/56
Filters
- Type Furnished
11
Throwaway
Throwaway
Throwaway
(No.) Size Recommended
(2) 20 x 25 x 1
10
(2) 20 x 25 x 1
10
(4) 16 x 25 x 2
Refrigerant Charge
(Lbs of R-22)
7
4.7
4.9
7.1
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
which is based on ARI Standard 210/240 except AK (380V/ 60 Hz) units.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YSC060A1,3,4,W Oversized Motor and YSC060AK Standard Motor Fan Diameter is 12 x 11.
9. Motor RPM shown is low speed. High speed RPM is 1100/1135.
10. Filter size shown is for low and medium heat models. High heat model filter size recommended is 20 x 30 x 1.
11. Optional 2” pleated filters also available.
12. YSC072A when used in a horizontal application has an EER of 10.1 and System Power (kW) of 6.83.
13. Medium heat is not available for AK (380V/ 60 Hz) units.
14. Outdoor motor is 0.75 hp for AK (380V/60 Hz) units.
15. Outdoor motor is 0.40 hp for AK (380V/60 Hz) units.
16. Standard Motor is 1.00 hp for YSC060AK (380V/ 60 Hz) units.
17. Standard Motor is 2.00 hp for the YSC072AK (380V/ 60 Hz) units.
General