45

RT-PRC006-EN

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-33 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & High Static Drive Kit
(or 2 HP oversized Motor& Drive)

1920

952

1.01

985

1.09

1019

1.17

1050

1.26

1080

1.34

1110

1.42

1139

1.51

1167

1.60

1192

1.68

1220

1.77

2160

977

1.17

1010

1.26

1043

1.36

1073

1.44

1103

1.53

1133

1.63

1161

1.72

1189

1.81

1216

1.91

1242

2.00

2400

1004

1.34

1037

1.44

1068

1.55

1099

1.65

1128

1.75

1156

1.85

1185

1.95

1212

2.05

1239

2.16

1265

2.26

2640

1033

1.54

1064

1.64

1095

1.75

1125

1.87

1153

1.97

1182

2.09

1210

2.20

2880

1065

1.76

1096

1.88

1124

1.99

1153

2.10

1182

2.22

2-HP Oversized Motor & Drive

Table PD-33 — Belt Drive Evaporator Fan Performance — 6 Ton — YSC072A3,A4,AW *H—  High Heat — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied Low Static Drive (1

)

1-HP Standard Motor & Drive

1920

559

0.32

618

0.39

668

0.46

715

0.53

759

0.61

802

0.69

842

0.77

881

0.85

917

0.93

2160

600

0.42

654

0.49

705

0.57

749

0.65

791

0.73

831

0.81

870

0.90

907

0.99

943

1.08

2400

594

0.46

644

0.53

692

0.61

741

0.70

786

0.79

826

0.88

864

0.97

900

1.05

936

1.15

971

1.24

2640

643

0.60

691

0.67

734

0.76

778

0.85

822

0.95

862

1.05

899

1.14

935

1.24

967

1.33

1001

1.43

2880

693

0.76

737

0.84

778

0.93

818

1.03

858

1.13

898

1.24

935

1.35

970

1.45

1003

1.55

1034

1.66

2-HP Oversized
Motor & Drive

Performance
Data

(6 Ton)
Standard Efficiency

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-32 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1 HP Standard Motor  & Drive

1HP Standard  Motor & High Static  Drive Kit

(or 2 HP Oversized Motor & Drive)

1920

931

0.96

965

1.04

999

1.12

1030

1.20

1062

1.29

1092

1.37

1120

1.45

1150

1.54

1177

1.63

1204

1.71

2160

951

1.10

984

1.19

1018

1.29

1049

1.37

1080

1.46

1110

1.55

1139

1.65

1168

1.74

1196

1.84

1222

1.93

2400

973

1.25

1006

1.35

1039

1.45

1070

1.55

1100

1.65

1129

1.76

1158

1.86

1186

1.96

1213

2.06

1241

2.16

2540

996

1.42

1029

1.52

1060

1.63

1091

1.74

1121

1.85

1150

1.96

1178

2.07

1206

2.18

1233

2.30

2880

1023

1.62

1054

1.72

1085

1.83

1114

1.95

1143

2.06

1172

2.18

1200

2.30

2 HP Oversized Motor & Drive

Table PD-32 — Belt Drive Evaporator Fan Performance — 6 Ton — YSC072A3,A4,AW *L,M — Low and Medium Heat —Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied Low Static Drive (1

)

1-HP Standard Motor & Drive

1920

583

0.35

638

0.42

687

0.49

732

0.56

777

0.64

817

0.71

857

0.80

895

0.88

2160

559

0.36

613

0.43

666

0.51

715

0.59

759

0.67

800

0.75

841

0.83

879

0.92

915

1.01

2400

597

0.46

647

0.54

695

0.62

743

0.71

788

0.80

828

0.88

866

0.97

902

1.06

938

1.15

2640

585

0.49

636

0.59

684

0.66

728

0.75

772

0.84

815

0.94

856

1.03

894

1.13

930

1.23

963

1.32

2880

629

0.63

677

0.73

722

0.81

763

0.89

803

0.99

844

1.09

884

1.20

923

1.31

958

1.41

990

1.51

Содержание YSC060A1

Страница 1: ...Packaged Gas Electric Rooftop Units Precedent 3 10T ons 60 Hz RT PRC006 EN October 2004...

Страница 2: ...lity as the original Micro with additional benefits for greater application flexibility With its sleek compact cabinet rounded corners and beveled top Precedent continues to provide the highest standa...

Страница 3: ...cation Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Heating Performance Controls Electric Power Dimension andWeights Me...

Страница 4: ...Disconnect Switch Two Inch Pleated Filters Factory or Field Installed Options Clogged Filter Fan Failure Switch Differential Pressure Switches DischargeAir Sensing Kit Economizer Electric Heaters Fros...

Страница 5: ...jumper betweenTest 1 andTest 2 terminals on the LowVoltage Terminal Board and the unit will walk through its operational steps automatically The unit automatically returns control to the zone sensor a...

Страница 6: ...wires and diagnosing the unit Outstanding Standard and Optional Components Compressors Precedent contains the best compressor technology available to achieve the highest possible performance Our compr...

Страница 7: ...overpressurization problems ProgressiveTubular Heat Exchanger The compact cabinet features a tubular heat exchanger in low medium and high heat capacities The heat exchanger is fabricated using stain...

Страница 8: ...moke detector or fire control panel The ventilation override kit is available as a field installed accessory Zone Sensors Available in programmable automatic and manual styles Precedent offers ultimat...

Страница 9: ...Electrical option with an Electrical Heater the heater must be factory installed Powered or Unpowered Convenience Outlet This option is a GFCI 120v 15amp 2 plug convenience outlet either powered or u...

Страница 10: ...ge Cooling Standard or High Efficiency Cooling available Economizer Equipped with either dry bulb reference or comparative enthalpy sensing this feature provides free cooling as the outdoor temperatur...

Страница 11: ...unit return air section also increases opening the dampers and relieving the conditioned space NOTE THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED PRESSUR...

Страница 12: ...hen round up to the nearest unit size 58 MBh 12 MBh approx 5 tons Step 3 Examine gross capacity Table PD 13 shows that aYHC060A4 has a gross cooling capacity of 62 4 MBh and 48 4 MBh sensible capacity...

Страница 13: ...52 25 db 57 84 wb Step 3b Determine leaving unit temperature in standard cooling mode Repeat Step 3a substituting net sensible or latent capacity for gross sensible or latent capacity to find the lea...

Страница 14: ...Oversized Motor 2 Optional Belt Drive Motor DIGIT 16 Hinged Service AccessFilters 0 Standard Panels Standard Filters A Hinged Access Panels Standard Filters B Standard Panels 2 Pleated Filters C Hing...

Страница 15: ...on Pipe Size in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Compressor No Type 1 Hermetic 1 Hermetic 1 Scroll 1 Scroll Outdoor Sound Rating dB 6 83 83 86 82 Outdoor Coil Type Lanced Lanced Lanced...

Страница 16: ...basedonARIStandard210 240exceptAK 380V 60Hz 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Stand...

Страница 17: ...10 0 14 0 10 0 14 0 10 0 14 0 Gas Connection Pipe Size in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 3 4 Compressor No Type 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 6 84 84 88 Outdoor Coil Type Lanced...

Страница 18: ...10 240 or 360 Units are rated at 80 F ambient 80 F entering dry bulb and 67 F entering wet bulb at ARI rated cfm 4 Heating Performance limit settings and rating data were established and approved unde...

Страница 19: ...81 80 81 81 81 No Burners 3 3 4 3 3 4 3 3 4 No Stages 1 2 2 1 2 2 1 2 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 10 0 14 0 Gas...

Страница 20: ...ceptAK 380V 60Hz units 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Uni...

Страница 21: ...utput Btu 121 500 162 000 202 500 AFUE 5 81 81 81 Steady State Efficiency 81 81 81 No Burners 3 4 5 No Stages 2 2 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 LP minimum maximum 10 0 14...

Страница 22: ...tandard210 240exceptAK 380V 60Hz 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240...

Страница 23: ...y 8 81 81 81 81 81 81 No Burners 2 2 3 2 2 3 No Stages 1 1 1 1 1 1 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 Gas Connection Pipe Size in...

Страница 24: ...ordance with the Unitary Air Conditioner Equipment certification program which is basedonARIStandard210 240 2 SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Heating Perf...

Страница 25: ...No Burners 2 2 3 2 2 3 2 3 3 No Stages 1 1 1 1 1 1 1 1 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 10 0 14 0 Gas Connection Pip...

Страница 26: ...its are certified in accordance with the Unitary Air Conditioner Equipment certification program whichisbasedonARIStandard210 240 2 EER and or SEER are rated at ARI conditions and in accordance with D...

Страница 27: ...0 1 750 1 750 1 750 1 750 3 450 Motor Frame Size Standard Oversized 56 56 56 56 56 56 Filters Type Furnished 1 1 Throwaway Throwaway Throwaway No Size Recommended 4 20 x 25 x 2 4 20 x 25 x 2 4 20 x 25...

Страница 28: ...31 5 31 7 31 6 36 3 24 2 90 40 2 40 2 40 4 39 2 42 3 30 1 38 8 38 8 38 8 38 8 40 9 30 2 37 1 37 1 37 0 37 0 39 1 30 3 34 6 34 6 34 6 34 6 36 6 30 0 75 36 4 32 6 39 4 23 5 41 1 15 1 33 2 31 0 37 7 23...

Страница 29: ...an heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 2 Gross Cooling Capacities MBH 4 Ton Single Phase YSC048A1...

Страница 30: ...or fan heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 5 Gross Cooling Capacities MBH 6 Ton Three Phase YSC072...

Страница 31: ...refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity 7 Ton Standard Efficiency Performance Data Table PD 7 Gross Cooling Capacities MBH 7 Ton Dual Compresso...

Страница 32: ...o appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 9 Gross Cooling Capacities MBH 10 Ton Three Phase YSC120A3 A4 AW AK AmbientTemperature F 85 95 105 115...

Страница 33: ...heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 10 Gross Cooling Capacities MBH 3 Ton YHC036A1 A3 A4 AW Ambien...

Страница 34: ...For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 13 Gross Cooling Capacities MBH 5 Ton Three Phase YHC060A3 A4 AW Am...

Страница 35: ...la refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 15 Gross Cooling Capacities MBH 7 Ton Dual Compressors Three Phase YHC092A3 A4 AW AmbientTem...

Страница 36: ...propriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 17 Gross Cooling Capacities MBH 10 Ton Three Phase YHC120A3 A4 AW AmbientTemperature F 85 95 105 115 Enter...

Страница 37: ...7 0 28 0 94 0 41 0 86 0 47 1080 0 73 0 38 0 50 0 29 0 91 0 43 0 82 0 39 1140 0 69 0 39 0 42 0 29 0 88 0 44 0 77 0 40 3 YSC036A L M 1200 0 66 0 40 0 34 0 30 0 84 0 45 0 74 0 41 Downflow Airflow 1260 0...

Страница 38: ...8 0 89 0 41 0 81 0 47 1080 0 68 0 38 0 45 0 29 0 86 0 43 0 77 0 39 1140 0 64 0 39 0 37 0 29 0 83 0 44 0 72 0 40 3 YSC036A H 1200 0 61 0 40 0 29 0 30 0 79 0 45 0 69 0 41 Downflow Airflow 1260 0 55 0 41...

Страница 39: ...93 1182 1 00 1214 1 07 1440 1113 0 90 1146 0 97 1178 1 04 1209 1 11 1240 1 18 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data i...

Страница 40: ...270 1 21 1299 1 28 1440 1217 1 10 1250 1 18 1281 1 27 1311 1 35 1339 1 43 1 HP Standard Motor Field Supplied High Static Drive 2 Table PD 22 Belt Drive Evaporator Fan Performance 3 Ton YSC036A3 A4 AW...

Страница 41: ...1265 1 31 1760 1185 1 19 1215 1 26 1246 1 33 1275 1 41 1304 1 49 1920 1230 1 37 1260 1 45 1 HPStandardMotor Field SuppliedHighStaticDrive 2 For Standard Evaporator Fan Speed RPM reference Table PD 86...

Страница 42: ...308 1 34 1338 1 43 1600 1268 1 26 1300 1 35 1331 1 44 1760 1321 1 47 1920 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 26 Belt Drive Evaporator Fan Performance 4 Ton YSC048A3 A4 AW L M Lo...

Страница 43: ...M BHP RPM BHP 1 HPStandardMotor Drive 1600 1158 1 05 1 190 1 13 1221 1 20 1251 1 27 1281 1 35 1800 1216 1 28 1246 1 35 1276 1 43 2000 2200 2400 For Standard Evaporator Fan Speed RPM reference Table PD...

Страница 44: ...ed External Static Pressure Inches of Water 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandard Motor Drive 1600 1274 1 28 1307 1 37 1338 1 46 1800 2000 2200 2400 Table P...

Страница 45: ...0 1 45 1003 1 55 1034 1 66 2 HPOversized Motor Drive Performance Data 6Ton Standard Efficiency For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to stan...

Страница 46: ...data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressur...

Страница 47: ...4 2 11 2540 1058 1 56 1090 1 68 1121 1 79 1152 1 90 1184 2 01 1214 2 13 1244 2 24 2880 1093 1 78 1123 1 90 1152 2 02 1181 2 14 1211 2 27 2 HPOversizedMotor Drive For Standard Evaporator Fan Speed RPM...

Страница 48: ...786 0 91 818 0 99 857 1 08 900 1 18 939 1 30 976 1 41 1009 1 51 1042 1 61 1073 1 71 1103 1 82 2 HP Standard Motor High Static Drive Table PD 38 Continued External Static Pressure Inches of Water 1 10...

Страница 49: ...1208 2 81 1236 2 95 1261 3 07 1287 3 21 1311 3 33 3 HPOversizedMotor Drive 3 HPOversizedMotor For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to stan...

Страница 50: ...1126 2 43 1157 2 57 1185 2 70 1212 2 83 3 HPOversizedMotor Drive 2 HPStandardMotor HighStaticDrive or3 HPOversizedMotor Table PD 43 Belt Drive Evaporator Fan Performance 7 Ton YSC090 092A3 A4 AW AK L...

Страница 51: ...HP Standard Motor High Static Drive Kit Motor Drive or3 HPOversizedMotor Drive 2400 1101 1 59 1134 1 69 1166 1 80 1 197 1 90 1229 2 02 1259 2 13 1287 2 25 1317 2 37 1344 2 48 1373 2 61 2700 1148 1 92...

Страница 52: ...ors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected For Standard Evaporator Fan Speed RPM reference Table PD 86...

Страница 53: ...n motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 49 Continued External Static Pressure Inches...

Страница 54: ...93 5 06 4800 1139 3 80 1161 4 00 1185 4 22 1208 4 43 1230 4 63 1253 4 85 1275 5 06 1295 5 27 1317 5 49 1337 5 71 5 HPOversizedMotor Drive Table PD 51 Continued External Static Pressure Inches of Water...

Страница 55: ...8 1342 4 76 1363 4 94 1383 5 11 1401 5 28 4400 1250 4 28 1280 4 52 1307 4 75 1334 4 98 1359 5 20 1384 5 43 1405 5 62 4800 1305 5 03 1334 5 28 1361 5 54 For Standard Evaporator Fan Speed RPM reference...

Страница 56: ...00 0 37 0 95 0 68 1 17 0 18 0 97 2400 0 26 0 97 0 55 1 20 960 0 74 0 36 0 56 0 28 0 89 0 38 0 82 0 35 1020 0 69 0 37 0 49 0 28 0 85 0 39 0 77 0 36 1080 0 65 0 38 0 44 0 29 0 82 0 41 0 74 0 38 1140 0 6...

Страница 57: ...7 0 50 1 20 960 0 74 0 36 0 56 0 28 0 89 0 38 0 82 0 35 1020 0 69 0 37 0 49 0 28 0 85 0 39 0 77 0 36 1080 0 65 0 38 0 44 0 29 0 82 0 41 0 74 0 38 1140 0 61 0 39 0 37 0 29 0 77 0 43 0 69 0 40 3 YHC036A...

Страница 58: ...SheaveAK69required FieldSuppliedBeltmaybe necessary 2 FieldSuppliedFanSheaveAK41required FieldSuppliedBeltmaybe necessary Factory supplied motors in commercial equipment are definite purpose motors sp...

Страница 59: ...49 922 0 55 970 0 62 1016 0 69 1059 0 77 1099 0 84 1138 0 92 1174 1 00 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 59 Continued External Static Pressure Inches of Water 1 10 1 20 1 30 1...

Страница 60: ...ur fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 61 Belt Drive Evaporator Fan Performance...

Страница 61: ...247 1 18 1278 1 26 1309 1 35 1337 1 43 1600 1268 1 27 1300 1 35 1332 1 45 1760 1320 1 47 1920 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 63 Continued External Static Pressure Inches of...

Страница 62: ...tors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 65 Belt Drive Evaporator Fan Performance 5 Ton YH...

Страница 63: ...isance tripping or premature motor failure Our product s warranty will not be affected Table PD 67 Continued External Static Pressure Inches of Water 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM B...

Страница 64: ...our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 68 Belt Drive Evaporator Fan Performanc...

Страница 65: ...Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to standard filters and wet coils No accessories or options are included in pressure drop data Refer to Table PD 89 to determi...

Страница 66: ...888 1 70 918 1 85 3600 658 0 84 695 0 96 731 1 08 764 1 20 796 1 33 828 1 47 859 1 63 890 1 79 920 1 94 949 2 10 2 HPStandardMotor Drive Table PD 73 Belt Drive Evaporator Fan Performance 7 Ton YHC092...

Страница 67: ...rs as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 75 Belt Drive Evaporator Fan Performance 7 Ton YHC0...

Страница 68: ...our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 77 Belt Drive Evaporator Fan Performance 8 Ton YHC102A3 A4 AW M M...

Страница 69: ...motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 79 Belt Drive Evaporator Fan Performance 8 Ton...

Страница 70: ...as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 81 Belt Drive Evaporator Fan Performance 8 Ton YHC102A...

Страница 71: ...964 2 50 991 2 66 1016 2 83 1040 3 00 1065 3 18 1090 3 38 1114 3 58 1138 3 79 1161 4 00 1184 4 22 5 HPOversizedMotor Drive For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data inclu...

Страница 72: ...wn in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected 3 HPStandardMotor Drive Table PD 85 Belt Drive Evaporator Fan Perform...

Страница 73: ...90 1150 1211 Factory set at 3 turns open Table PD 87 Standard Motor High Static Drive Accessory Sheave Fan Speed Rpm Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn T ons Model No Open Open Open Open Op...

Страница 74: ...060A 2000 0 06 0 10 0 10 0 18 0 07 0 18 0 02 2400 0 09 0 14 0 14 0 26 0 10 0 26 0 04 1920 0 04 0 07 0 10 0 01 0 06 0 02 6 Y C072A 2400 0 06 0 09 0 11 0 02 0 08 0 02 2880 0 09 0 12 0 13 0 04 0 10 0 04...

Страница 75: ...092A1 A3 A4 AW M 150 0 105 121 5 85 25 55 Y C090 092A1 A3 A4 AW AK H 200 0 140 162 0 113 35 65 Standardand Y C102A1 A3 A4 AW AK L 120 0 84 97 2 68 15 45 8 High Efficiency Y C102A1 A3 A4 AW M 150 0 10...

Страница 76: ...6 16 4 16 2 16 0 15 7 15 4 2400 15 6 15 4 15 2 15 1 14 9 14 6 14 3 Tons SCFM 35 40 45 50 55 60 65 2400 16 7 17 3 18 0 18 7 19 3 20 1 20 9 2700 14 9 15 5 16 1 16 7 17 3 18 0 18 7 7 3000 13 1 13 7 14 2...

Страница 77: ...ors This sensor includes a digital display of set point adjustment and space temperature in F Fahrenheit or C Celsius Includes FAN and SYSTEM buttons supports the service functions of the standard sen...

Страница 78: ...e Heat Anticipator Automatic Changeover One Heat Two CoolThermostat Off Auto System Switch Auto On Fan Switch Programmable Electronic Night Setback Thermostat Heating setback and cooling setup with 7...

Страница 79: ...0 14 4 20 13 6 20 YSC048AW 517 633 9 8 15 10 6 15 10 0 15 YSC060A1 187 253 47 3 60 49 0 60 YSC060A3 187 253 31 5 50 33 6 50 30 3 45 5 YSC060A4 414 506 16 0 25 16 3 25 15 6 25 YSC060AW 517 633 12 2 15...

Страница 80: ...15 7 7 15 7 7 15 YHC048A1 187 253 29 4 45 31 5 50 YHC048A3 187 253 21 2 30 23 3 35 22 6 35 4 YHC048A4 414 506 11 0 15 12 6 15 11 8 15 YHC048AW 517 633 8 3 15 9 1 15 8 5 15 YHC060A1 187 253 39 5 60 41...

Страница 81: ...2 2 Y C036A4 1 460 3 1 0 2 5 16 1 Y C036AW 1 575 3 1 0 1 7 13 2 Y C048A3 1 208 230 3 1 0 5 0 32 2 4 Y C048A4 1 460 3 1 0 2 5 16 1 Y C048AW 1 575 3 1 0 1 7 13 2 Y C060A3 1 208 230 3 1 0 5 0 32 2 5 Y C0...

Страница 82: ...1 3450 11 4 64 1 1 40 1 1 4 3 YSC072A3 1 208 230 3 6 3450 19 0 156 1 1 70 3 85 9 30 6 YSC072A4 1 460 3 6 3450 10 1 75 1 1 70 2 50 5 80 YSC072AW 1 575 3 6 3450 7 7 54 1 1 70 1 54 3 60 YSC072AK 1 380 3...

Страница 83: ...33 2 0 6 6 5 YHC060A4 1 460 3 4 5 3450 7 8 59 6 1 1 33 1 2 2 5 YHC060AW 1 575 3 4 5 3450 6 2 49 4 1 1 33 0 9 1 5 YHC072A3 1 208 230 3 5 7 3450 20 7 156 1 1 70 3 85 9 30 6 YHC072A4 1 460 3 5 7 3450 10...

Страница 84: ...A L M Y C090 092 102A L 1 1 35 3000 3000 208 230 1 0 6 Y C072A H Y C090 092 102A M H 2 1 15 3500 208 230 1 0 42 Y C120A L M H Table ED 8 Electrical Characteristics Power Exhaust T ons Volts Phase HP R...

Страница 85: ...cal electrical codes Wiring shown dotted is to be furnished and installed by the customer Typical Number Of Wires ZoneSensors A ManualChangeover 4 Manual AutoChangeover 5 Manual AutoChangeoverwith Sta...

Страница 86: ...millimeters 1775 3 4 and 5 Ton Standard Efficiency Low and Medium Heat 3 and 4 Ton High Efficiency Low and Medium Heat 1775 3 4 and 5 Ton Standard Efficiency High Heat 3 and 4 Ton High Efficiency Hig...

Страница 87: ...dimensions are in inches millimeters Dimensional Data 3 5 Tons Downflow Airflow Supply and Return Through the Base Utilities 3 5 Tons Unit Clearance and Roof Opening 3 5Tons 3 5 Tons Horizontal Airflo...

Страница 88: ...RT PRC006 EN 88 Dimensional Data 3 5 Tons Downflow Duct Connections Field Fabricated 3 5Tons All dimensions are in inches millimeters 3 5 Tons Roof Curb...

Страница 89: ...T PRC006 EN Dimensional Data 6 10Tons 6 Ton Standard and High Efficiency 7 Ton Standard Efficiency All dimensions are in inches millimeters 7 Ton High Efficiency 8 and 10 Ton Standard and High Efficie...

Страница 90: ...nsional Data All dimensions are in inches millimeters 6 10 Tons Downflow Airflow Supply and Return Through the Base Utilities 6 10 Tons Horizontal Airflow Supply and Return 6 10 Tons Unit Clearance an...

Страница 91: ...PRC006 EN Dimensional Data 6 10Tons All dimensions are in inches millimeters 6 10 Tons Roof Curb 6 10 Tons Downflow Duct Connections Field Fabricated 857 857 S U P P L Y R E T U R N ALL FLANGES 1 1 4...

Страница 92: ...conomizer Manual or Motorized Damper Hood 3 5 Tons Barometric Relief Damper Hood 3 5 Tons Swing Diameter for Hinged Door s Option 3 5 Tons Height of Gas Pipe required from Inside Base of Unit to Gas S...

Страница 93: ...Tons Height of Gas Pipe required from Inside Base of Unit to Gas Shut off assembly Factory Provided 6 10 Tons Economizer and Barometric Relief Damper Hoods 6 10 Tons Power Exhaust 21 3 8 543 MM 17 432...

Страница 94: ...0 957 310 252 175 220 40 22 YSC120A 1063 958 317 261 177 202 41 21 10 YHC120A 1203 1060 342 277 197 245 40 22 Notes 1 Corner weights are given for information only 2 Weights are approximate Table W 2...

Страница 95: ...it nameplate voltage Crankcase heater internal temperature and current sensitive motor overloads shall be included for maximum protection Compressors shall have internal spring isolation and sound muf...

Страница 96: ...ol algorithm maintains accurate temperature control minimizes drift from set point and provides better building comfort A centralized Microprocessor shall provide anti short cycle timing and time dela...

Страница 97: ...The assembly includes fully modulating 0 100 percent motor and dampers minimum position setting preset linkage wiring harness with plug spring return actuator and fixed dry bulb control The barometri...

Страница 98: ...in hood and screen shall provide up to 50 percent outside air Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air Once set outdoor air dampers sha...

Страница 99: ...99 RT PRC006 EN...

Страница 100: ...fort trane com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Super...

Отзывы: