61
RT-PRC006-EN
(4 Ton)
High Efficiency
Performance
Data
Table PD-62— Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1)
1-HP Standard Motor & Drive
1280
681
0.26
755
0.32
816
0.38
870
0.45
921
0.51
968
0.58
1013
0.65
1053
0.72
1091
0.79
1127
0.86
1440
748
0.36
817
0.43
876
0.49
927
0.56
976
0.63
1022
0.70
1065
0.78
1106
0.85
1144
0.93
1180
1.01
1600
816
0.47
879
0.55
937
0.62
987
0.70
1033
0.78
1076
0.85
1119
0.93
1158
1.01
1197
1.10
1233
1.18
1760
885
0.61
943
0.69
999
0.78
1049
0.86
1093
0.94
1135
1.03
1174
1.11
1213
1.20
1250
1.29
1286
1.38
1920
956
0.77
1009
0.86
1062
0.96
1110
1.05
1154
1.14
1195
1.23
1232
1.32
1269
1.41
1304
1.50
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
1-HP Standard Motor & Field Supplied High Static Drive (2)
Table PD-62 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard
Motor & Drive
1280
1162
0.94
1193
1.01
1225
1.09
1255
1.16
1284
1.23
1440
1214
1.09
1247
1.18
1278
1.26
1309
1.35
1337
1.43
1600
1268
1.27
1300
1.35
1332
1.45
—
—
—
—
1760
1320
1.47
—
—
—
—
—
—
—
—
1920
—
—
—
—
—
—
—
—
—
—
1-HP Standard Motor & Field Supplied High Static Drive (2)
Table PD-63 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard
Motor & Drive
1280
1169
0.96
1201
1.03
1231
1.10
1262
1.17
1290
1.24
1440
1222
1.11
1256
1.20
1286
1.28
1317
1.37
1346
1.45
1600
1278
1.29
1311
1.38
1342
1.48
—
—
—
—
1760
—
—
—
—
—
—
—
—
—
—
1920
—
—
—
—
—
—
—
—
—
1-HP Standard Motor & Field Supplied High Static Drive (2)
Table PD-63 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1)
1-HP Standard Motor & Drive
1280
698
0.28
769
0.34
828
0.40
881
0.46
932
0.52
978
0.59
1021
0.66
1061
0.73
1099
0.81
1134
0.88
1440
767
0.37
834
0.44
890
0.51
941
0.58
988
0.65
1034
0.72
1077
0.80
1116
0.87
1153
0.95
1190
1.03
1600
837
0.50
899
0.57
955
0.65
1003
0.72
1048
0.80
1091
0.88
1132
0.96
1171
1.04
1209
1.12
1245
1.21
1760
908
0.64
966
0.73
1020
0.81
1067
0.89
1110
0.98
1151
1.06
1190
1.15
1228
1.23
1264
1.32
1300
1.41
1920
981
0.82
1035
0.91
1085
1.00
1133
1.09
1174
1.18
1213
1.27
1250
1.37
1286
1.46
—
—
—
—
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.