RT-PRC006-EN
72
Performance
Data
(10 Ton)
High Efficiency
Table PD-84 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1
)
3200
—
—
777
1.15
814
1.28
853
1.42
895
1.59
936
1.76
973
1.93
1008
2.09
1037
2.24
1064
2.38
3600
819
1.42
857
1.57
890
1.71
922
1.85
957
2.02
994
2.20
1032
2.39
1067
2.58
1099
2.77
1131
2.96
4000
902
1.91
936
2.07
968
2.23
998
2.39
1027
2.55
1058
2.73
1091
2.93
1124
3.14
1158
3.36
1189
3.57
4400
986
2.50
1016
2.68
1047
2.86
1075
3.03
1101
3.20
1128
3.39
1155
3.58
1186
3.80
1217
4.03
1246
4.25
4800
1070
3.22
1098
3.40
1127
3.60
1153
3.79
1178
3.98
1203
4.17
1227
4.37
1251
4.57
1279
4.80
1307
5.05
5-HP Oversized Motor & Drive
Table PD-84 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Drive
3200
1090
2.53
1115
2.67
1139
2.81
1161
2.95
1183
3.09
1205
3.23
1225
3.37
1246
3.51
1265
3.65
1284
3.78
3600
1157
3.13
1181
3.29
1205
3.45
1228
3.61
1250
3.77
1272
3.93
1293
4.09
1312
4.24
1331
4.40
1351
4.56
4000
1218
3.78
1246
3.99
1271
4.18
1294
4.36
1317
4.55
1338
4.72
1360
4.91
1379
5.07
1398
5.25
1418
5.43
4400
1276
4.49
1304
4.73
1333
4.97
1359
5.20
1383
5.42
1405
5.62
—
—
—
—
—
—
—
—
4800
1336
5.30
1363
5.56
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
3-HP Standard Motor& Drive
Table PD-85 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Field Supplied
3-HP Standard Motor & Drive
Low Static Drive (1
)
3200
785
1.18
821
1.31
861
1.46
903
1.62
944
1.80
981
1.96
1014
2.12
1043
2.27
1070
2.41
1095
2.55
3600
874
1.64
907
1.78
939
1.93
977
2.11
1014
2.30
1050
2.49
1084
2.69
1115
2.87
1144
3.05
1169
3.21
4000
964
2.21
994
2.37
1023
2.53
1053
2.71
1087
2.91
1121
3.12
1154
3.33
1185
3.55
1215
3.76
1242
3.96
4400
1055
2.91
1082
3.08
1109
3.25
1135
3.43
1164
3.64
1194
3.86
1225
4.09
1255
4.32
1284
4.56
1312
4.79
4800
1146
3.74
1171
3.92
1196
4.11
1220
4.31
1244
4.51
1271
4.73
1298
4.97
1327
5.22
1354
5.47
1382
5.74
5-HP Oversized Motor & Drive
Table PD-85 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Drive
3200
1120
2.70
1143
2.84
1166
2.98
1188
3.12
1208
3.25
1229
3.39
1249
3.53
1269
3.67
1289
3.82
1308
3.96
3600
1194
3.37
1217
3.53
1240
3.69
1262
3.85
1282
4.01
1303
4.17
1322
4.32
1341
4.48
1361
4.64
1378
4.79
4000
1269
4.16
1292
4.34
1314
4.52
1335
4.70
1356
4.88
1377
5.06
1397
5.24
1415
5.41
—
—
—
—
4400
1339
5.02
1365
5.25
1388
5.47
1410
5.67
—
—
—
—
—
—
—
—
—
—
—
—
4800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.