RT-PRC006-EN
26
(5 - 6 Tons)
High Efficiency
Table GD-6 — Continued
5 Ton Convertible Units
6 Ton Convertible Units
YHC060A1
YHC060A3, A4, AW
YHC072A3, A4, AW
Direct Drive Indoor Fan
- Type
FC Centrifugal
FC Centrifugal
—
No. Used/Diameter (in.)
1/11 x 11
8
1/11 x 11
8
—
Drive Type/No. Speeds
Direct/2
Direct/2
—
No. Motors
1
1
—
Motor HP (Standard/Oversized)
0.90/1.00
0.90/1.00
—
Motor RPM (Standard/Oversized)
985/1,080
9
985/1,080
9
—
Motor Frame Size (Standard/Oversized)
48/48
48/48
——
Belt Drive Indoor Fan
- Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used/Diameter (in.)
1/11 x 11
1/11 x 11
1/12 x 12
Drive Type/No. Speeds
Belt/Variable Sheave
11
Belt/Variable Sheave
11
Belt/Variable Sheave
No. Motors
1
1
1
Motor HP (Standard/Oversized)
1.00/—
1.00/—
1.00/2.00
Motor RPM (Standard/Oversized)
1,750/—
1,750/—
1750,1750
Motor Frame Size (Standard/Oversized)
56/—
56/—
56/56
Filters
- Type Furnished
Throwaway
Throwaway
Throwaway
(No.) Size Recommended
(2)20 x 30 x 1
12
(2) 20 x 30 x 1
12
(4) 16 x 25 x 2
12
Optional Hot Gas Reheat Coil
- Type
15
—
Lanced
—
Tube Size (in.)OD
—
0.375
—
Face Area (sq. ft.)
—
2.22
—
Rows/FPI
—
2/16
—
Refrigerant Charge
(Lbs of R-22)
7
Standard
7.9
8.4
10.7
Optional Hot Gas Reheat Coil
—
10.7
—
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
which is based on ARI Standard 210/240.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings
shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YHC060A Oversized Motor Fan Diameter is 12 x 11.
9. Motor RPM shown is low speed. High speed Motor RPM is 1,100/1,135.
10. YHC072A when applied in a horizontal configuration has an 11.3 EER and 6.2 System Power (kW).
11. Belt Drive Motor is not available for YHC060A1.
12. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
13. With Dehumidification (Hot Gas Reheat) option: Direct/2.
14. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
15. Available on three-phase only.
General
Data