RLC-SVU01B-E4
48
Diagnostics
D9
1E1
1E2
5A0
5A1
1E6
1E8
1E5
1E7
A1
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
NonLatch
The main processor has
successfully come out of a
reset and built its application. A
reset may have been due to a
power up, installing new
software or configuration. This
diagnostic is immediately and
automatically cleared and thus
can only be seen in the Historic
Diagnostic List in TechView.
Info
Remote
MP: Reset Has
Occurred
Latch
The Intermediate Oil Pressure
Transducer for this compressor
is reading a pressure either
above its respective circuit's
Condenser Pressure by 1.05 bar
or more, or below its
respective Suction Pressure 0.7
bar or more for 30 seconds
continuously.
Immediate
Local
Oil Flow Fault -
Compressor 1A
Latch
Same as Oil Flow Fault -
Compressor 1A
Immediate
Local
Oil Flow Fault -
Compressor 1b
Latch
Same as Oil Flow Fault -
Compressor 1A
Immediate
Local
Oil Flow Fault -
Compressor 2A
Latch
Same as Oil Flow Fault -
Compressor 1A
Immediate
Local
Oil Flow Fault -
Compressor 2b
Latch
Bad Sensor or LLID
Normal
Remote
Oil Temperature
Sensor - Cprsr 1B
Latch
Bad Sensor or LLID
Normal
Remote
Oil Temperature
Sensor - Cprsr 2B
Latch
Bad Sensor or LLID
Normal
Remote
Oil Temperature
Sensor - Cprsr 1A
Latch
Bad Sensor or LLID
Normal
Remote
Oil Temperature
Sensor - Cprsr 2A
Latch
Bad Sensor or LLID. Note that if
this diagnostic occurs,
operational pumpdown will be
performed regardless of the
last valid temperature.
Normal
Remote
Outdoor Air
Temperature Sensor