RLC-SVU01B-E4
51
Diagnostics
1A3
8C
8D
1B2
1B3
1B4
1B5
5CD
6A7
5CE
6A8
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
NonLatch
Same as Power Loss -
Compressor 1A
Immediate
Remote
Power Loss -
Compressor 2B
NonLatch
The pumpdown cycle for this
circuit was terminated
abnormally due to excessive
time or due to a specific set of
diagnostic criteria - but without
associated latching diagnostics.
Info
Remote
Pumpdown
Terminated - Circuit 1
NonLatch
Same as Pumpdown
Terminated - Circuit 1
Info
Remote
Pumpdown
Terminated - Circuit 2
Latch
A 30% Current Imbalance has
been detected on one phase
relative to the average of all 3
phases for 90 continuous
seconds.
Immediate
Local
Severe Current
Imbalance -
Compressor 1A
Latch
Same as Severe Current
Imbalance - Compressor 1A
Immediate
Local
Severe Current
Imbalance -
Compressor 1B
Latch
Same as Severe Current
Imbalance - Compressor 1A
Immediate
Local
Severe Current
Imbalance -
Compressor 2A
Latch
Same as Severe Current
Imbalance - Compressor 1A
Immediate
Local
Severe Current
Imbalance -
Compressor 2B
Latch
Starter has had a loss of
communication with the MP for
a 15 second period.
Immediate
Local
Starter 1A Comm
Loss: MP
Latch
While in the Starter Dry Run
Mode either 50% Line Voltage
was sensed at the Potential
Transformers or 10% RLA
Current was sensed at the
Current Transformers.
Immediate
Local
Starter 1A Dry Run
Test
Latch
Starter has had a loss of
communication with the MP for
a 15 second period.
Immediate
Local
Starter 1B Comm
Loss: MP
Latch
While in the Starter Dry Run
Mode either 50% Line Voltage
was sensed at the Potential
Transformers or10 % RLA
Current was sensed at the
Current Transformers.
Immediate
Local
Starter 1B Dry Run
Test