RLC-SVU01B-E4
54
Diagnostics
1E9
1EA
1EB
1EC
1ED
1EE
1EF
1F0
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
This is a specific starter test
where 1M(1K1) is closed first
and a check is made to ensure
that there are no currents
detected by the CT's. If currents
are detected when only 1M is
closed first at start, then one of
the other contactors is shorted.
Immediate
Local
Starter Fault Type I -
Compressor 1A
Latch
Same as Starter Fault Type I -
Compressor 1A
Immediate
Local
Starter Fault Type I -
Compressor 1B
Latch
Same as Starter Fault Type I -
Compressor 1A
Immediate
Local
Starter Fault Type I -
Compressor 2A
Latch
Same as Starter Fault Type I -
Compressor 1A
Immediate
Local
Starter Fault Type I -
Compressor 2B
Latch
This is a specific starter test
where the Shorting Contactor
(1K3) is individually energized
and a check is made to ensure
that there are no currents
detected by the CT's. If current
is detected when only S is
energized at Start, then 1M is
shorted. b. This test in a. above
applies to all forms of starters
(Note: It is understood that
many starters do not connect
to the Shorting Contactor.).
Immediate
Local
Latch
Same as Starter Fault Type II -
Compressor 1A
Immediate
Local
Starter Fault Type II -
Compressor 1B
Latch
Same as Starter Fault Type II -
Compressor 1A
Immediate
Local
Starter Fault Type II -
Compressor 2A
Latch
Same as Starter Fault Type II -
Compressor 1A
Immediate
Local
Starter Fault Type II -
Compressor 2B
Starter Fault Type II -
Compressor 1A