RLC-SVU01B-E4
53
Diagnostics
CD
180
181
182
183
6A3
6A4
6A5
6A6
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
NonLatch
Same as Starter Contactor
Interrupt Failure - Compressor
2A
Special
Mode
Remote
Starter Contactor
Interrupt Failure -
Compressor 2B
Latch
The Starter Module did not
receive a transition complete
signal in the designated time
from its command to transition.
The must hold time from the
Starter Module transition
command is 1 second. The
Must trip time from the
transition command is 6
seconds. Actual design is 2.5
seconds. This diagnostic is
active only for Y-Delta, Auto-
Transformer, Primary Reactor,
and X-Line Starters.
Immediate
Local
Starter Did Not
Transition -
Compressor 1A
Latch
Same as Starter Did Not
Transition - Compressor 1A
Immediate
Local
Starter Did Not
Transition -
Compressor 1B
Latch
Same as Starter Did Not
Transition - Compressor 1A
Immediate
Local
Starter Did Not
Transition -
Compressor 2A
Latch
Same as Starter Did Not
Transition - Compressor 1A
Immediate
Local
Starter Did Not
Transition -
Compressor 2B
Latch
Starter failed to arm or start
within the allotted time
(15 seconds).
Info
Local
Starter Failed to
Arm/Start - Cprsr 1A
Latch
Same as Starter Failed to
Arm/Start - Cprsr 1A
Info
Local
Starter Failed to
Arm/Start - Cprsr 1B
Latch
Same as Starter Failed to
Arm/Start - Cprsr 1A
Info
Local
Starter Failed to
Arm/Start - Cprsr 2A
Latch
Same as Starter Failed to
Arm/Start - Cprsr 1A
Info
Local
Starter Failed to
Arm/Start - Cprsr 2B