687
68C
68D
69A
69B
68A
698
68B
699
5D9
5DA
RLC-SVU01B-E4
33
Diagnostics
Latch
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Operate the remaining
fans as fixed speed fan deck.
Comm Loss: Fan
Inverter Fault, Circuit
#1 or Circuit #1,
Drive 1
Special
Mode
Remote
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Special
Mode
Remote
Comm Loss: Fan
Inverter Fault, Circuit
#1, Drive 2
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Special
Mode
Remote
Comm Loss: Fan
Inverter Fault, Circuit
#2 or Circuit #2,
Drive 1
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Special
Mode
Remote
Comm Loss: Fan
Inverter Fault, Circuit
#2, Drive 2
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Normal
Remote
Comm Loss: Fan
Inverter Fault, Circuit
#1, Drive 1 and 2
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Normal
Remote
Comm Loss: Fan
Inverter Power,
Circuit #2 or Circuit
#2 Drive 1 and 2
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Remote
Comm Loss: Fan
Inverter Speed
Command, Circuit #1
or Circuit #1 Drive 1
and 2
Latch
Same as Comm Loss: Fan
Inverter Fault, Circuit #1 or
Circuit #1, Drive 1
Special
Mode
Remote
Comm Loss: Fan
Inverter Speed
Command, Circuit #2
or Circuit #2 Drive 1
and 2
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Comm Loss: Female
Step Load
Compressor 1A
Special
Mode
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Comm Loss: Female
Step Load
Compressor 1B
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Comm Loss: Fan
Control Circuit #2,
Stage #4