5E6
696
697
5E2
690
691
692
693
6AC
6AB
RLC-SVU01B-E4
36
Diagnostics
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Comm Loss: Oil
Temperature, Circuit
#2 or Cprsr 2A
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Comm Loss: Oil
Temperature,
Cprsr 1B
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Comm Loss: Oil
Temperature,
Cprsr 2B
Latch
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Note that if this
diagnostic occurs, operational
pumpdown will be performed
regardless of the last valid
temperature.
Normal
Remote
Comm Loss: Outdoor
Air Temperature
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Local
Comm Loss:
Starter 1A
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Local
Comm Loss:
Starter 1B
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Local
Comm Loss:
Starter 2A
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Local
Comm Loss:
Starter 2B
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Info
Local
Comm Loss: Starter
Panel High
Temperature Limit -
Panel 1, Cprsr 1B
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Info
Local
Comm Loss: Starter
Panel High
Temperature Limit -
Panel 1, Cprsr 2A