RLC-SVU01B-E4
47
Diagnostics
B8
BA
BB
BC
BD
1AD
6A1
5FF
6A2
69C
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
Same as Low Suction
Refrigerant Pressure - Circuit 1
Immediate
Local
Low Suction
Refrigerant Pressure -
Circuit 2B
Latch
Compressor current exceeded
overload time vs. trip
characteristic. For A/C products
Must trip = 140% RLA, Must
hold=125%, nominal trip132.5%
in 30 seconds.
Immediate
Local
Motor Current
Overload -
Compressor 1A
Latch
Same as Low Suction
Refrigerant Pressure - Circuit 1
Immediate
Local
Motor Current
Overload -
Compressor 1B
Latch
Same as Low Suction
Refrigerant Pressure - Circuit 1
Immediate
Local
Motor Current
Overload -
Compressor 2A
Latch
Same as Low Suction
Refrigerant Pressure - Circuit 1
Immediate
Local
Motor Current
Overload -
Compressor 2B
Latch
Memory error criteria
Immediate
Remote
MP Application
Memory CRC Error
Latch
MP has determined there was
an error with the previous
power down store. Starts and
Hours may have been lost for
the last 24 hours.
Info
Remote
MP: Could not Store
Starts and Hours
Latch
MP has an invalid configuration
based on the current software
installed.
Immediate
Remote
Latch
MP has determined there was
an error with a block in the
Non-Volatile memory. Check
settings.
Info
Remote
MP: Non-Volatile
Block Test Error
Latch
MP has determined there was
an error in a sector of the Non-
Volatile memory and it was
reformatted. Check settings.
Info
Remote
MP: Non-Volatile
Memory Reformat
MP: Invalid
Configuration