Scope & Definitions of Configurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Note 1.
If “high temperature inhibit” is configured, or set auxiliary input as “inhibit high
temperature stop” and this input is active, when temperature is higher than the preset
value, or high temperature alarm input is active, controller will send warning signal only
and not stop the unit.
Note 2.
If “low oil pressure inhibit” is configured, or set auxiliary input as “inhibit low oil
pressure stop” and this input is active, when oil pressure is lower than the preset value,
or low oil pressure alarm input is active, controller will send warning signal only and not
stop the unit.
Note 3.
If “3P3W” is selected, maximum shutdown threshold of “Gens Over Voltage” can
be set as 620V; when select others, maximum shutdown threshold can be set as 360V.
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS
Form 2
No
Items
Description
0
Not Used
Output port is deactivated when “Not Used” is selected.
1
Common Alarm
Include all shutdown alarms and warning alarms. When there is warning
alarm only, it is not self-lock; when a shutdown alarm occurs, it is self-lock
until the alarm is reset.
2
Energized to Stop
Suitable for genset with electromagnet and will active after “stop idle
delay”. It is deactivated when the “ETS Solenoid delay” expires.
3
Idle Control
Used for engine which has idles. Close before starting and open in warm-
ing up delay; Close during stop idle delay and open when stop is complet-
ed.
4
Preheat Control
Close before starting and open before power up;
5
Close Generator
When close time is 0, it’s continuous output.
6
Reserved
7
Open ATS
When close time is 0, it’s disabled.
8
Raise Speed
Close when the generator enters into Warming Up delay (close time:
warming up delay) while open when Aux. Raise Speed input is active.