Scope & Definitions of Configurable Parameters
7.2 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL ACTIVE WHEN
CONNECT TO GRAND (B-))
Form 3
No
Items
Description
0
Not Used
1
High Temperature Input
If these signals are active after safety on delay, shutdown alarm will be im-
mediately initiated.
2
Low Oil Pressure Input
3
Warn Input
Only warning and not shutdown if this input is active.
4
Shutdown input
Shutdown alarm will be immediately initiated if this input is active.
5
WTH STOP by cool
When the genset is running normally and this signal is activated, if there is
a high temperature situation, the controller will first cool down the gen-
erator and then stop it; if the signal is deactivated and a high temperature
situation occurs, the controller will shut down the gen-set without cooling
down.
6
Generator Closed input
7
Reserved
8
Inhibit High
Temperature Stop
When it is active, high temperature shutdown will be prohibited. Note 1
9
Inhibit Low Oil
Pressure Stop
When it is active, low oil pressure shutdown will be prohibited. Note 2
10
Remote Start
11
Fuel Level Warn
12
Coolant Level Warn
13
Fuel Level Shutdown
14
Coolant Level
Shutdown
15
Inhibit Start Auto
In Auto mode, if this input is active, whether remote start signal activates
or not, the controller will not give a start command to the generator. If
generator is normal running, stop command won’t be executed. When this
input is deactivated, genset will automatically start or stop.
21