Scope & Definitions of Configurable Parameters
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS continued
Form 2 continued
No
Items
Description
9
Drop Speed
Close when the generator enters into Stop Idle delay/ Energized to Stop
delay (close time: Stop Idle delay) while open when Aux. Drop Speed input
is active.
10
Generator Run
Action when genset is normal running while deactivated when engine
speed is lower than the “crank disconnect speed”.
11
Fuel Pump Control
Close when fuel level is lower than the “Fuel Pump On” value or when low
fuel level warning input is active; Open when fuel level is higher than the
“Fuel Pump Off” and low fuel level warning input is deactivated;
12
High Speed Control
Close when the generator enters into Warming Up delay while open after
cooling delay.
13
In Auto Mode
The controller is in automatic mode.
14
Fuel Relay Output
To control fuel relay output.
15
Choke Control
Start to output in cranking period; in addition, during safety on running,
output for preset delay.
16
Reserved
17
Reserved
20