Wiring Connections
Continued:
No.
Function
Cable Size
Remarks
10
Aux. Input 1
1.0mm
2
Ground connected is active (B-)
Details see
form 3
11
Aux. Input 2
1.0mm
2
Ground connected is active (B-)
12
Aux. Input 3
1.0mm
2
Ground connected is active (B-)
13
Aux. Input 4
1.0mm
2
Ground connected is active (B-)
14
Aux. Input 5
1.0mm
2
Ground connected is active (B-)
15
GND
The common port of sensor; (B-) has already connected.
16
CHARGER(D+)
1.0mm
2
Connected with charger starter’s D+ (WL) terminals. Being
hang up If there is no this terminal.
17
MP2
1.0mm
2
(B-) has already connected. Connected with Speed sensor,
shielding line is recommended.
18
MP1
1.0mm
2
Connected with Speed sensor, shielding line is recommend-
ed.
19
S11
1.0mm
2
Connect to stepper motor. S11 and S12 are belong to one
phase to the motor while S21 and S22 are belong to the
other phase.
20
S12
1.0mm
2
21
S21
1.0mm
2
22
S22
1.0mm
2
23
RS232 RX
0.5mm
Connected to GSM module.
24
RS232 TX
0.5mm
25
RS232 GND
0.5mm
26
Gens AC Voltage (U)
1.0mm
2
Connected to U-phase of generator (2A fuse is recommend-
ed).
27
Gens AC Voltage (V)
1.0mm
2
Connected to V-phase of generator (2A fuse is recommend-
ed).
28
Gens AC Voltage (W)
1.0mm
2
Connected to W-phase of generator (2A fuse is recommend-
ed).
29
Gens AC Voltage (N)
1.0mm
2
Connected to N-phase of generator (2A fuse is recommend-
ed).
NOTE:
LINK interface is parameters configured interface that can be programmed by
PC using an SG72 adapter. If there is need to remote control the genset, please use the
SG485 module produced by our company.
13
032-5094-1A-EN