Scope & Definitions of Configurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No
Items
Range
Default
Description
25
Charge Alt Failure
(Warning)
(0-30)V
6.0
During generator is normal running, when alternator
D+(WL) voltage has fallen below the set value and
remains for 5s, It will initiate a shutdown alarm signal.
26
Battery Over
Voltage (Warning)
(12-40)V
33.0
When battery voltage has exceeded the set value and
remains for 20s, It will initiate a warning alarm signal.
Only warning and not to shutdown the generator.
27
Battery Under Volt-
age (Warning)
(4-30)V
8.0
When battery voltage has fallen below the set value
and remains for 20s, It will initiate a warning alarm
signal. Only warning and not to shutdown the gener-
ator.
28 Auxiliary Output 1
(0-17)
15
Factory default: Choke Control
29 Auxiliary Output 2
(0-17)
2
Factory default: Energized To Stop
30 Auxiliary Output 3
(0-17)
3
Factory default: Idle Control
31 Auxiliary Output 4
(0-17)
5
Factory default: Close Generator
32 Auxiliary Input 1
(0-15)
1
Factory default: High Temperature Input
33
Auxiliary Input 1
Active
(0-1)
0
Factory default: Close to active
34
Auxiliary Input 1
Delay
(0-20.0)s
2.0
35 Auxiliary Input 2
(0-15)
2
Factory default: Low Oil Pressure Input
36
Auxiliary Input 2
Active
(0-1)
0
Factory default: Close to active
37
Auxiliary Input 2
Delay
(0-20.0)s
2.0
38 Auxiliary Input 3
(0-15)
10
Factory default: Remote Start
39
Auxiliary Input 3
Active
(0-1)
0
Factory default: Close to active
40
Auxiliary Input 3
Delay
(0-20.0)s
2.0
41 Auxiliary Input 4
(0-15)
11
Factory default: Fuel Level Warn
16