Scope & Definitions of Configurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No
Items
Range
Default
Description
42
Auxiliary Input 4
Active
(0-1)
0
Factory default: Close to active
43
Auxiliary Input 4
Delay
(0-20.0)s
2.0
44 Auxiliary Input 5
(0-15)
3
Factory default: Warn Input
45
Auxiliary Input 5
Active
(0-1)
0
Factory default: Close to active
46
Auxiliary Input 5
Delay
(0-20.0)s
2.0
47 Power On Mode
(0-2)
0
0: Stop Mode
1: Manual Mode
2: Auto Mode
48 Module Address
(1-254)
1
Communication address of controller.
49 Passwords
(0-9999)
1234
50 Crank Disconnect
(0-2)
2
There are 2 conditions of disconnecting starter with
engine: Generator Frequency and Speed Sensor. Each
condition can be used alone and simultaneously to
separating the start motor and genset as soon as
possible. See Table 4.
51
Disconnect Engine
Speed
(0-3000)
r/min
360
When the engine speed has exceeded the set value,
starter will be disconnected.
52
Disconnect Genera-
tor Freq
(10.0-30.0)Hz
14.0
When the generator frequency has exceeded the set
value, starter will be disconnected.
53 High Temp. Inhibit
(0-1)
0
Factory default: High Temp. Shutdown. When high
temperature occurs, shutdown alarm is active. Note 1
54 Low OP Inhibit
(0-1)
0
Factory default: when low oil pressure occurs, shut-
down alarm is active. Note 2
55 Voltage Input
(0-3)
0
0: 3P4W; 1: 2P3W
2: 1P2W; 3: 3P3W Note 3
56 Rated Speed
(0-6000)
r/min
1500
Offer standard to adjust rated speed.
17
032-5094-1A-EN