Protection
5.2 SHUTDOWN ALARM continued
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator.
Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No.
Type
Description
12
No gens freq
When the controller detects the generator frequency is 0, it will initiate a
shutdown alarm and the alarm information will be displayed on the LCD.
13
Low Fuel Level
When the controller detects that the fuel level is lower than the set value or
there is Low Fuel Level input, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
14
Low Coolant Level
When the controller detects that there is Low Coolant Level input, it will
initiate a shutdown alarm and the alarm information will be displayed on the
LCD.