Scope & Definitions of Configurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No
Items
Range
Default
Description
57 Idle Speed
(0-6000) r/
min
900
Offer standard to adjust idle speed.
58 Idle Slope
0-6000
10
The rising speed rate during the process of genset
change idle running status into rated speed running
status.
59 Idle Gain
1-1000
150
The gain is regulated during the genset is idle run-
ning.
60 Crank Angle
(0-90)°
45
The throttle opening before the genset is starting.
61 Crank Disc. Angle
(0-90)°
35
The initial opening of the throttle after the genset is
started.
62 Proportional Gain
1-3000
1100
The regulated gain when the genset is running in
rated speed.
63 Integral Gain
1-3000
20
64 Differential Gain
1-3000
1
65 Total Gain
1-1000
100
66 Window
(1-1000)
r/min
1
67 Window Gain
1000-3000
1950
68 Position Gain
0-1000
0
69 Compensate Gain
0-100
0
70 Scheduled Enable
(0-1)
0
Factory default: Disable
71 Scheduled Run Mode
(0-1)
0
Factory default: Off Load
72 Schedule Period
(0-2)
0
Factory default: 0 Monthly
73 Schedule Day
(1-31)
1
74 Schedule Week
(0-6)
0
Factory default: 0 Daily
75 Schedule Hour
(0-23)
0
76 Schedule Minute
(0-59)
0
77 Schedule Duration
(0-9999)
0
78 GSM Set
(0-1)
0
Factory default: Disable
18
032-5094-1A-EN