Scope & Definitions of Configurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
No
Items
Range
Default
Description
1
Start Delay
(0-3600)s
1
Time from remote start signal is active to start gen-
set.
2
Stop Delay
(0-3600)s
1
Time from remote start signal is deactivated to gen-
set stop.
3
Start Attempts
(1-10)times
3
Maximum crank times of crank attempts. When reach
this number, controller will send start failure signal.
4
Preheat Delay
(0-300)s
0
Power-on time of heater plug before starter is pow-
ered up.
5
Choke Time
(0-300)s
0
Power-on time of choke after crank succeeds.
6
Cranking Time
(3-60)s
8
Power-on time of starter
7
Crank Rest Time
(3-60)s
10
The waiting time before second power up when en-
gine start fail.
8
Safety On Delay
(1-60)s
10
Alarms for low oil pressure, high temperature, under
speed, under frequency/voltage, charge alt failure
are inactive.
9
Start Idle Time
(0-3600)s
0
Idle running time of genset when starting.
10 Warming Up Time
(0-3600)s
10
Warming time between genset switch on and high
speed running.
11 Cooling Time
(3-3600)s
10
Radiating time before genset stop, after it unloads.
12 Stop Idle
(0-3600)s
0
Idle running time when genset stop.
13 ETS Solenoid Hold
(0-120)s
20
Stop electromagnet’s power on time when genset is
stopping.
14 Fail to Stop Delay
(0-120)s
0
Time between ending of genset idle delay and
stopped when “ETS time” is set as 0; Time between
ending of ETS hold delay and stopped when “ETS
time” is not 0.
15 Close Time
(0-10)s
5.0
Pulse width of generator switch on. When it is 0,
means output constantly.
14