62
RLC-SVX07A-EN
Installation - Electrical
Installer-Supplied Components
The installer must provide the following components if not ordered with the
unit:
•
Power supply wiring (in conduit) for all field-wired connections.
•
All control (interconnecting) wiring (in conduit) for field supplied devices.
•
Fused-disconnect switches.
•
Power factor correction capacitors.
Power Supply Wiring
All power supply wiring must be sized and selected accordingly by the project
engineer in accordance with National Electric Code.
All wiring must comply with local codes and the National Electrical Code. The
installing (or electrical) contractor must provide and install the system inter-
connecting wiring, as well as the power supply wiring. It must be properly
sized and equipped with the appropriate fused disconnect switches. The type
and installation location(s) of the fused disconnects must comply with all
applicable codes.
Cut holes for the appropriately-sized wiring conduits in the upper right side of
the power connection panel on the RTWA and RTUA units. The wiring is
passed through these conduits and connected to the terminal blocks or
optional unit-mounted disconnect. Refer to Figures
3
thru
6
and Figures
8
and
9
.
For the RTCA units, refer to Figure
11
for the power supply wiring hole
location.
Control Power Supply
The RTWA and RTUA units are equipped with a control power transformer. It
is not necessary to provide control power voltage to these units.
Water Pump Power Supply
Provide power supply wiring with fused-disconnect for the chilled water
pump(s) (RTWA and RTUA) and condenser water pump(s) (RTWA only).
Interconnecting Wiring
Chilled Water Pump
CAUTION
Equipment Damage!
The chiller water pump must operate for a minimum of one
minute after the UCM receives a command through the external
Auto/Stop input to shut down the chilled water system. Do not
use the proof of chiller water flow interlock (1U1 TB3-1 and -2) by
itself as the normal means of terminating chiller operation. Failure
to continue pump operation for one minute after unit shut down
may result in evaporator freeze up.
On the RTWA and RTUA units, the controller will initiate the “RUN:UNLOAD”
mode to terminate a cycle from any of the following:
- STOP key pressed
- Loss of load
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...