114
RLC-SVX07A-EN
Controls Interface
Current Overload Protection
The UCM continually monitors compressor current to provide unit protection
in the event of an overcurrent or locked rotor condition. Protection is based on
the phase with the highest current and, if limits are exceeded, the UCM will
shutdown the compressor and will display an MMR diagnostic.
Leaving Chilled Water Temperature Control
If the Auto key is pressed and a remote chilled water setpoint has been
communicated, the UCM will control to the Remote Chiller Water Setpoint.
Otherwise, it will control to the front panel setpoint. Control is accomplished
by both staging compressors and modulating the slide valves on each
compressor.
Upon start-up, if the leaving chilled water temperature is dropping 5 F per
minute or faster, the chiller will not load further.
Chilled Water Reset (CWR)
As an option, the UCM will reset the chilled water temperature setpoint,
based on either the return water temperature, zone air temperature, or
outdoor air temperature. The 1U2 Module is necessary to preform CWR.
The following are selectable:
1.
One of four RESET TYPEs, from top to bottom in order of reset:
no CWR
RETURN WATER TEMPERATURE RESET
OUTDOOR AIR TEMPERATURE RESET
The Clear Language Display will not permit more than one type of reset to be
selected in the Operator Settings Menu.
2.
RESET RATIO Setpoints. For OUTDOOR AIR TEMPERATURE RESET,
there are both positive and negative reset ratios.
3.
START RESET Setpoints
4.
MAXIMUM RESET Setpoints. The maximum resets are with respect to
the chilled water setpoint.
No matter which type of reset is selected all parameters are factory set to a
predetermined set of values. Field adjustment of 2, 3, or 4 above, is usually
not required.
Table 25
Compressor(s) Current Limit Setpoints
vs. Chiller Current Limit Setpoint (CLS)
System
CLS
(70 - 125)
Number of compressors
in operation
One
Two
120%
120
120
100%
120
100
80%
120
80
60%
120
60
40%
80
40
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...