RLC-SVX07A-EN
115
Controls Interface
The equations for each type of reset are:
RETURN WATER TEMPERATURE RESET
CWS' = CWS + RESET RATIO
[START RESET - (TWE - TWL)]
and CWS' > or = CWS
and CWS' - CWS < or = MAXIMUM RESET
OUTDOOR AIR TEMPERATURE RESET
CWS' = CWS + RESET RATIO
[START RESET - TOD]
and CWS' > or = CWS
and CWS' - CWS < or = MAXIMUM RESET
CWS' is the new chilled water setpoint.
CWS is the active chilled water setpoint before any reset has occurred.
RESET RATIO is a user adjustable gain.
START RESET is a user adjustable reference.
TOD is the outdoor temperature.
TWE is the entering evaporator water temperature.
TWL is the leaving evaporator water temperature.
MAXIMUM RESET is a user adjustable limit, providing the maximum amount
of reset.
NOTE:
When any type of CWR is enabled, the UCM will step the CWS
toward the desired CWS' (based on the above equations and setup
parameters) at a rate of 1 F every 5 minutes. This applies when the chiller is
both running and off. Normally the chiller will start at the Differential-to-Start
value above a fully reset CWS or CWS'.
The values for RESET RATIO for each type of reset are:
Reset Type
Reset
Ratio Range
Increment
English Units
Increment
SI Units
Factory Default
Value
Return
1O to 120%
1%
1%
50%
Outdoor
80 to -80%
1%
1%
10%
The values for START RESET for each type of reset are:
Reset Type
Start
Reset Range
Increment
English Units
Increment
SI Units
Factory Default
Value
Return
4 TO 30 F
1F
0.1C
10F (5.6 C)
(2.2 to 16.7 C)
Outdoor
50 to 130 F
1F
0.1 C
90F (32.2 C)
(10 to 54.4 C)
The values for MAXIMUM RESET for each type of reset are:
Reset
Type
Maximum
Reset Range
Increment
English Units
Increment
SI Units
Factory Default
Value
Return
1O to 20 F
1F
0.1C
5F (2.8 C)
(-17.8 to -6.7 C)
Outdoor
O to20 F
1F
0.1 C
5F (2.8 C)
(-17.8 to -6.7 C)
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...