128
RLC-SVX07A-EN
Start-Up Procedures
subcooling is also low. If the operating pressures, sight glass, superheat
and subcooling readings indicate a refrigerant shortage, gas-charge refrig-
erant into each circuit, as required. With the unit running, add refrigerant
vapor by connecting the charging line to the suction service valve and
charging through the backseat port until operating conditions become
normal.
NOTE:
If both suction and discharge pressures are low but subcooling is
normal, a problem other than refrigerant shortage exists. Do not add refrig-
erant, as this may result in overcharging the circuit.
NOTE:
Use only refrigerants specified on the unit nameplate, to prevent
compressor damage and insure full system capacity.
•
If operating conditions indicate a refrigerant overcharge, remove refriger-
ant at the liquid line service valve. Allow refrigerant to escape slowly, to
minimize oil loss. Do not discharge refrigerant into the atmosphere.
System Superheat
Normal suction superheat for each circuit is approximately 6 F (4 F for RTUA
units) at full operating load. Superheat temperature can be expected to be
moving around the 6 F (4 F for RTUA) setpoint when the chiller is pulling
down or the compressor slide valve is being modulated. Superheat can be
expected to settle out at approximately 6 F (4 F for RTUA units) when the
above items stabilize.
System Subcooling
Normal subcooling for each circuit ranges from 6 F to 8 F, depending on the
unit. If subcooling for either circuit does not approximate these figures, check
the superheat for the circuit and adjust, if required. If superheat is normal but
subcooling is not, contact a qualified service technician.
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...