RLC-SVX07A-EN
123
Pre-Start Checkout
•
Fill the evaporator and condenser chilled water circuits. Refer to Table
1
for liquid capacities. Vent the system while it is being filled. Open the
vents on the top of the evaporator and condenser during filling and close
when filling is completed.
Customer Note
The use of improperly treated or untreated water in this equipment may
result in scaling, erosion, corrosion, algae or slime. The services of a qualified
water treatment specialist should be engaged to determine what treatment,
if any, is advisable. The Trane Company warranty specifically excludes liability
of corrosion, erosion or deterioration of Trane equipment. Trane assumes no
responsibilities for the results of the use of untreated or improperly treated
water or saline or brackish water.
CAUTION:
Equipment Damage!
Do not use untreated or improperly treated water. Equipment
damage may occur.
•
Close the fused-disconnect switch(es) that supplies power to the chilled
water pump starter and the condenser water pump starter.
•
For RTCA units, close the fused-disconnect switches that supply power
to the fans.
•
Start the chilled water pump and condenser water pump to begin circula-
tion of the water. Inspect all piping for leakage and make any necessary
repairs.
•
With water circulating through the system, adjust water flow and check
water pressure drop through the evaporator and condenser. Refer to
Figures
16
,
17
and
18
.
•
Adjust the chilled water flow switch and condenser water flow switch (if
installed) for proper operation.
•
Prove all Interlock and Interconnecting Wiring Interlock and External as
described in Section
“Installation - Electrical”
.
•
Check and set, as required, all Clear Language Display Menu Items.
•
Stop the chilled water pump and condenser water pump.
Unit Voltage Power Supply
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...