Diagnostics
Low Oil Flow - Cprsr A
CMR
The differential oil pressure switch remained opened for more
than 20 contiguous seconds on Cprsr A.
Note: Although GP cmprs do not have pressure switch or Oil
Line solenoid, this diagnostic is still active. The input must be
jumpered for normal operation on GP cmprs.
Low Oil Flow - Cprsr B
CMR
Same as Diagnostic for Cprsr A, above, but Cprsr B.
Low Oil Flow - Cprsr C
CMR
Same as Diagnostic for Cprsr A, above, but Cprsr C.
Low Oil Flow - Cprsr D
CMR
Same as Diagnostic for Cprsr A, above, but Cprsr D.
Low Pressure Cutout - Ckt 1
CMR
The low pressure switch opened or remained open past the
ignore time during compressor operation (after one retry) or
the low pressure switch was open prior to compressor start
with Sat Cond Temp above -18F.
Low Pressure Cutout - Ckt 2
CMR
Same as Ckt 1.
Low Superheat - Ckt 1
CMR
A low superheat condition existed for an extended period of
time. If a superheat less than or equal to 2 degrees F (1.11
degrees C) is detected for more than 2400 degree F seconds,
the circuit shall be shutdown. The integrated area (2400
Degree F seconds) shall be only below 2 degrees F superheat.
Low Superheat - Ckt 2
CMR
Same as Diagnostic for Ckt 1, above.
Memory Error Type I
IFW
On UCM either power up or following a Type II Memory Error a
NOVRAM memory error was detected. The UCM is operating
on all Engineering ROM defaults for all setup parameters.
Check all setup parameters and continue to run chiller. Replace
the Chiller Module as soon as a replacement is available.
NOTE:
It is expected that this diagnostic will be
detected on the very first power up of the Chiller
Module at the Manufacturer since the NOVRAM will
not contain valid data on first power up.
Memory Error Type II
IFW
A Shadow RAM memory error was detected. The UCM is
operating on all last valid values (pulled from NOVRAM) for all
setup parameters. No setup parameter changes were pending
to be loaded into NOVRAM, a complete recovery of all setup
parameters was made and there is no need to check unit setup
parameters. Compressor starts and hour were lost for not
more than the last 24 hours. This is expected to be an isolated
event and repair or replacement is not required. If this
diagnostic does occur repeatedly, then replace the Chiller
module.
Memory Error Type III
IFW
A Shadow RAM memory error was detected. The UCM is
operating on all last valid values (pulled from NOVRAM) for all
setup parameters. Setup parameter changes less than 24
hours old pending to be loaded into NOVRAM were lost. Check
all setup parameters made in the last 24 hours. Compressor
starts and hours were lost for not more than the last 24 hours.
This is expected to be an isolated event and repair or
replacement is not required. If this diagnostic does occur
repeatedly, then replace the Chiller module.
Table 28
Diagnostic Codes
Diagnostic Description
Type
Cause
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...