Installation - Remote Condenser
NOTE:
Table 7
states the equivalent length, in feet, for various non-ferrous
valves and fittings. When calculating the equivalent length, do not include
piping of the unit. Only field piping must be considered.
Liquid Line Sizing
The Trane Company recommends that the liquid line diameter be as small as
possible, while maintaining acceptable pressure drop. This is necessary to
minimize refrigerant charge. The total length between the components must
not exceed 200 actual feet or 300 equivalent feet. Refer to
Table
11
for the
maximum allowable liquid line drainable to the evaporator, listed in actual feet,
for applications with the condenser above the unit.
Liquid risers in the system will require an additional 0.5 psig pressure drop
per foot of vertical rise. The liquid line risers must not exceed 15 feet from the
base of the air-cooled condenser. The liquid line does not have to be pitched.
Liquid line sizing for these units are shown in
Tables
7
to
9
.
Liquid lines are not typically insulated. However, if the lines run through an
area of high ambient temperature (eg. boiler room), subcooling may drop
below required levels. In these situations, insulate the liquid lines.
NOTE:
In case of power failure to the expansion valve, the amount of liquid
refrigerant contained in the liquid line above the evaporator must not exceed
the holding capacity of the evaporator. Therefore, the actual length of the
drainable liquid in the liquid line is restricted to the above values.
Table 7
Equivalent Lengths of Non-ferrous Valves and Fittings
LINE SIZE
Inches OD
GLOBE
Valve (Ft)
ANGLE
Valve (Ft)
SHORT
Radius Elbow (Ft)
LONG
Radius Elbow (Ft)
1 1/8
87
29
2.7
1.9
1 3/8
102
33
3.2
2.2
1 5/8
115
34
3.8
2.6
2 1/8
141
39
5.2
3.4
2 5/8
159
44
6.5
4.2
3 1/8
185
53
8
5.1
3 5/8
216
66
10
6.3
4 1/8
248
76
12
7.3
Reproduced by permission of the Air Conditioning and Refrigeration Institute.
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...