116
RLC-SVX07A-EN
Controls Interface
Leaving Water Temperature Cutout
This temperature cutout provides protection against freezing caused by low
leaving water temperature. The setpoint is both factory set and adjustable
from the Service Settings Menu. Temperatures below the setpoint will cause
the UCM to accelerate reduction of chiller capacity, even to the point of
compressor shutdown. A non-latching diagnostic will be generated if the LWT
is below the cutout for more than 30 degree F seconds.
There must be a minimum of 5 F between the cutout temperature and both
the front panel and active chilled water setpoints. The Clear Language Display
will not permit setting of either the front panel or active chilled water temper-
atures less than 5 F above this cutout temperature. The second line will state
“Limited by Cutout Setpoint, (+) to change”.
If the leaving water temperature cutout is set upward, the Clear Language
Display will maintain the 5 F minimum and will automatically raise the
settings on the front panel and active chilled water setpoints, if necessary.
If the front panel or Active Chilled Water Setpoints were adjusted, the display
will show the following when the “Enter” key is pressed:
“FRONT PANEL CHILLED WATER SETPOINT
HAS BEEN INCREMENTED DUE TO CUTOUT
SETPOINT CHANGE”
If the leaving water temperature drops below the cutout setpoint while the
compressors are de-energized, it will produce an IFW diagnostic. If the
leaving water temperature drops below the cutout setpoint while the
compressors are energized for 30 F seconds, the unit will shut down on an
MAR diagnostic.
Low Refrigerant Temperature Cutout
Both circuits are protected from a saturated evaporator refrigerant temper-
ature that goes below this setting. The cutout setpoint must be a minimum of
15 F lower than the front panel or active chilled water setpoints. See
Table 26
for proper settings.
There must be a minimum of 15 F between the cutout temperature and both
the front panel and active chilled water setpoints. The Clear Language Display
will not permit setting of either the front panel or active chilled water temper-
atures less than 15 F above this cutout temperature and the display will flash
the last valid temperature.
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...