54
RLC-SVX07A-EN
Installation - Remote Condenser
Discharge (Hot Gas) Line Sizing
The discharge lines should pitch downward, in the direction of the hot gas
flow, at the rate of 1/2 inch per each 10 feet of horizontal run.
Discharge line size is based on the velocity needed to obtain sufficient oil
return. Basic discharge line sizing is shown in
Tables 11
and
12
, depending on
the unit configuration.
NOTE:
The proper column for leaving evaporator water temperature must
be used to avoid catastrophic damage to the unit. Columns for 0 F to 19 F and
20 F to 39 F can only be used on units designed for low temperature applica-
tions. Refer to the design conditions of the unit to determine the correct
column that must be used.
NOTE:
The discharge line should drop well below the compressor discharge
outlet before beginning its vertical rise. This prevents possible refrigerant
drainage back to the compressor and oil separator during the unit STOP cycle.
Refer to
Figures
23
,
24
and
25
for details.
Refrigerant Sensors
If a Trane RTCA condenser is used with the RTUA unit, no sensors need to be
field installed.
If a non-RTCA condenser is used, an outdoor ambient temperature sensor
and a saturated condenser temperature sensor must be installed for the
RTUA to control properly. The outdoor ambient temperature sensor must be
installed in a location that accurately represents the outdoor ambient temper-
ature which the condenser will encounter. It must not be exposed to direct
sunlight or precipitation which could artificially alter the actual outdoor
ambient temperature. Also, it must not be exposed to the recirculating air
from the discharge of the condenser.
The saturated condensing temperature sensors must be installed on the
refrigerant piping which leaves the condenser and enters the subcooler on
both circuits. Strap the sensor into place, similar to the method used with
most thermal expansion valve sensing bulbs. This sensor can be mounted
externally if it is sufficiently insulated. The insulation covering the sensor
must be capable of withstanding the higher temperatures without degra-
dation. Failure to properly mount and insulate the saturated condensing refrig-
erant temperature sensor could cause poor control and/or possible
compressor damage.
Table 13
Upflow Discharge Line Sizes (O.D.)
35 Ton Circuit
40 Ton Circuit
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
40 - 60 F
20 - 39 F
0 - 19 F
40 - 60 F
20 - 39 F
0 - 19 F
0 - 300 ft. 2 1/8
1 5/8
1 5/8
0 - 300 ft.
2 1/8
1 5/8
1 5/8
50 Ton Circuit
60 Ton Circuit
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
40 - 60 F
20 - 39 F
0 - 19 F
40 - 60 F
20 - 39 F
0 - 19 F
0 - 300 ft. 2 1/8
2 1/8
1 5/8
0 - 300 ft.
2 1/8
2 1/8
1 5/8
Содержание R Series
Страница 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Страница 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Страница 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Страница 26: ...26 RLC SVX07A EN Installation Mechanical Figure 11 Dimensions and Clearances for RTCA Condenser ...
Страница 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Страница 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Страница 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Страница 154: ...154 RLC SVX07A EN Diagnostics ...
Страница 156: ...156 RLC SVX07A EN 3332 ...
Страница 158: ...158 RLC SVX07A EN 3333 ...
Страница 160: ...160 RLC SVX07A EN 3334 ...
Страница 162: ...162 RLC SVX07A EN 3335 ...
Страница 164: ...164 RLC SVX07A EN 3336 ...
Страница 166: ...166 RLC SVX07A EN 5119 ...
Страница 168: ...168 RLC SVX07A EN 5143 ...
Страница 170: ...170 RLC SVX07A EN 5144 ...
Страница 172: ...172 RLC SVX07A EN 5145 ...
Страница 174: ...174 RLC SVX07A EN 5146 ...
Страница 176: ...176 RLC SVX07A EN 6008 ...
Страница 178: ...178 RLC SVX07A EN 6009 ...
Страница 180: ...180 RLC SVX07A EN 5147 ...
Страница 182: ...182 RLC SVX07A EN 6526 ...
Страница 184: ...184 RLC SVX07A EN 5150 ...
Страница 186: ...186 RLC SVX07A EN 6010 ...