Model Number Descriptions
8
RTHD-SVX01K-EN
Digit 37 – Flow Switch
X
=
No Flow Switch
A
=
Evaporator (NEMA 1)
B
=
Evaporator and Condenser
(NEMA 1)
C
=
Evaporator (NEMA 4)
D
=
Evaporator and Condenser
(NEMA 4)
Digit 38 – Factory Test
X
=
Standard Test
C
= Witness
Test
D
= Performance
Test
Digit 39 – Starter Type
Y
= Wye-Delta
Closed
Transition
Starter
V
=
Premium AFD
Historical information:
A
=
Solid State Starter
Digits 40,41,42 — Design RLA
(for starter)
*** = Selection
Assigned
Digit 43 – Power Line
Connection Type
A
= Terminal
Block
B
=
Mechanical Disconnect Switch
D
= Circuit
Breaker
F
=
High Interrupt Circuit Breaker
Historical information:
H
=
Ground Fault Circuit Breaker
J
=
Ground Fault High Interrupt
Circuit Breaker
Digit 44 – Max RLA (Starter)
C
=
277 max RLA (Fixed Speed)
E
=
364 max RLA (Fixed Speed)
G
=
126 max RLA (Drive and Panel)
H
=
150 max RLA (Drive and Panel)
J
=
185 max RLA (Drive and Panel)
K
=
234 max RLA (Drive and Panel)
L
=
279 max RLA (Drive and Panel)
M
=
316 max RLA (Drive and Panel)
N
=
366 max RLA (Drive and Panel)
Q
=
397 max RLA (Fixed Speed)
R
=
476 max RLA (Fixed Speed)
T
=
598 max RLA (Fixed Speed)
U
=
779 max RLA (Fixed Speed)
V
=
197 max RLA (Drive and Panel)
W =
241 max RLA (Drive and Panel)
X
=
292 max RLA (Drive and Panel)
Y
=
367 max RLA (Drive and Panel)
Z
=
446 max RLA (Drive and Panel)
1
=
549 max RLA (Drive and Panel)
2
=
176 max RLA (Drive and Panel)
3
=
223 max RLA (Drive and Panel)
4
=
280 max RLA (Drive and Panel)
5
=
335 max RLA (Drive and Panel)
6
=
411 max RLA (Drive and Panel)
7
=
455 max RLA (Drive and Panel)
Historical information - Enclosure Type:
F
=
NEMA 1 - MRLA207
G
=
NEMA 1 - MRLA277
H
=
NEMA 1 - MRLA300
J
=
NEMA 1 - MRLA364
K
=
NEMA 1 - MRLA397
L
=
NEMA 1 - MRLA476
M
=
NEMA 1 - MRLA500
N
=
NEMA 1 - MRLA598
P
=
NEMA 1 - MRLA779
Digit 45 – Under/Over Voltage
Protection
X
=
None
U
=
With Under/Over Voltage
Protection
Digit 46 – Operator Interface
T
=
Tracer AdaptiView™ TD7 Display
Historical information:
A
=
DynaView™ - English
B
= DynaView
-
French
C
= DynaView
-
Italian
D
= DynaView
-
Spanish
E
= DynaView
-
German
F
= DynaView
-
Dutch
G
= DynaView
-
Chinese
(traditional)
H
=
DynaView - Chinese (simple)
J
= DynaView
-
Japanese
K
=
DynaView - Portugese (Brazil)
L
= DynaView
-
Korean
M
= DynaView
-
Thai
Digit 47 – Digital
Communication Interface
X
=
None
5
= LonTalk
®
Interface
7
= BACnet
®
8
= Modbus™
Interface
Historical information:
4
=
Tracer
®
Comm 4 Interface
6
= BACnet
®
for CH530 Controls
Digit 48 – External Water &
Demand Limit Setpoint
X
=
None
2
=
2–10 Vdc input
4
=
4–20 mA input
Digit 49 – External Base Loading
X
=
None
2
=
2–10 Vdc input
4
=
4–20 mA input
Digit 50 – Ice Building
X
=
None
A
=
Ice Building with Relay
B
=
Ice Building without Relay
Digit 51 – Programmable Relays
X
=
None
R
=
With Programmable Relays
Digit 52 – Chilled Water Reset
X
=
Chilled Water Reset -
Return Water
T
=
Chilled Water Reset -
Outdoor Air Temperature
Digit 53 – Control Outputs
X
=
None
D
=
Chiller Differential Pressure &
Percent RLA
P
=
Condenser Pressure (% HPC) &
Percent RLA
V
=
Condenser Regulating Valve
Control & Percent RLA
Digits 54 – Refrigerant Monitor
Input
X
=
None
A
=
100 ppm / 4-20 mA
B
=
1000 ppm / 4-20 mA
C
=
100 ppm / 2-10 Vdc
D
=
1000 ppm / 2-10 Vdc
Digit 55 – Condenser Leaving
Hot Water Temp Control
X
=
None
H
=
Hot Water Temp Control
Digits 56,57,58 — AFD Output
Amps
000 = Not applicable (wye-delta starter)
*** = Selection Assigned
Compressor Model
Number
Digits 1,2,3,4— Compressor
Model
CHHC= Positive displacement,
helical rotary (twin screw)
hermetic compressor
Digit 5— Design Control
*
= Factory
Assigned
Digit 6— Frame Size
B
=
B Frame
C
=
C Frame
D
= D
Frame
E
= E
Frame
Digit 7— Capacity
1
=
Smaller capacity (minor)
2
=
Larger capacity (major)
3
=
Special 50 Hz
Digit 8 — Motor Voltage
A
= 200V/60Hz/3Ph
C
= 230V/60Hz/3Ph
D
= 380V/60Hz/3Ph
F
=
400/460V- 50/60Hz - 3Ph
used for 380V/50Hz/3Ph
H
= 575V/60Hz/3Ph
M
= 690V/50Hz/3Ph
B
= 525V/50Hz/3Ph
G
= 500V/50Hz/3Ph
S
= Special
voltage
Digit 9— Design Specials
0
= No
specials
C
=
All specials denoted by digits
elsewhere
S
=
Uncategorized special not
denoted by other digits
Digits 10,11— Design
Sequence
** = Factory
assigned
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...