RTHD-SVX01K-EN
17
Dimensions and Weights
Unit Dimensions
See unit submittals for specific unit dimensions and water
connection locations.
Unit Weights
Table 5.
Weights — standard units (wye-delta starter)
Unit Configuration
(a)
Shipping Weight
Operating Weight
lbs
kg
lbs
kg
B1B1B1
9,292
4,215
9,867
4,476
B1C1D1
9,837
4,462
10,554
4,787
B2B2B2
9,402
4,265
10,019
4,545
B2C2D2
9,953
4,515
10,653
4,832
C1D5E4
12,973
5,884
13,673
6,202
C1D6E5
12,780
5,797
13,397
6,077
C1E1F1
14,718
6,676
15,818
7,175
C2D3E3
14,002
6,351
15,044
6,824
C2D4E4
12,972
5,884
13,672
6,201
C2F2F3
16,168
7,334
17,560
7,965
D1D1E1
14,443
6,551
15,385
6,987
D1F1F2
16,187
7,342
17,537
7,955
D1G1G1
18,600
8,437
20,500
9,299
D1G2G2
19,107
8,667
21,065
9,555
D2D2E2
14,562
6,605
15,570
7,062
D2F2F3
16,820
7,629
18,220
8,264
D2G2G1
18,700
8,482
20,700
9,389
D2G3G3
19,508
8,849
21,641
9,816
D3D2E2
14,562
6,605
15,570
7,062
D3F2F3
16,820
7,629
18,220
8,264
D3G2G1
18,650
8,460
20,650
9,367
E3D2E2
14,720
6,677
15,728
7,134
E3F2F3
16,956
7,691
18,356
8,326
E3G2G1
18,800
8,528
20,800
9,435
E3G3G3
19,653
8,915
21,786
9,882
Notes:
1. All w/- 3%
2. Shipping weights include standard 150 psig water boxes, refrigerant charge and oil charge.
3. Operating weights include refrigerant, oil and water charges.
(a) Unit configuration digits 1, 2 - compressor code (also shown in unit model number digits 6, 7); digits 3, 4 - evaporator code (unit
model number digits 14, 15); digits 5, 6 - condenser code (unit model number digits 21, 22).
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...