Installation Mechanical
RTHD-SVX01K-EN
23
Important:
Rigging dimensions given in
are
given as a starting point reference. Lifting
cables should be adjusted as necessary for
even unit lift.
Note:
If absolutely necessary, the chiller can be pushed or
pulled across a smooth surface if it is bolted to
wood shipping mounts.
for unit shipping
weights.
Note:
Weights are typical for units with R-134a
charge.
mm
3658
3353
1612
99
654
610
D1G2G2
in
144 132 63.54
3.82
26.02
24
mm
3658
3353
1614
97
661
610
D2D2E2
in
120 108 59.96
7.4
24.17
24
mm
3048
2743
1523
188
614
610
D2F2F3
in
144 132 63.39
3.98
24.29
24
mm
3658
3353
1610
101
617
610
D2G2G1
in
144 132 63.46
3.9
25.75
24
mm
3658
3353
1612
99
654
610
D2G3G3
in
144 132 63.46
3.9
25.75
24
mm
3658
3353
1612
99
654
610
D3D2E2
in
120 108 60 7.4
24.17
24
mm
3048
2743
1523
188
614
610
D3F2F3
in
144 132 63.39
3.98
24.29
24
mm
3658
3353
1610
101
617
610
D3G2G1
in
144 132 63.46
3.9
25.75
24
mm
3658
3353
1612
99
654
610
E3D2E2
in
120 108 60 4.57
24.09
24
mm
3048
2743
1525
116
612
610
E3F2F3
in
144 132 63.46
1.14
24.21
24
mm
3658
3353
1612
29
615
610
E3G2G1
in
144 132 63.82
0.79
26
24
mm
3658
3353
1621
20
661
610
(a) Designator corresponds to digits 6, 7, 14, 15, 21 and 22 of model number.
Table 7.
Rigging dimensions (continued)
Unit
Configuration
(a)
Dimension - in (mm)
Units
A
B
C
D
E
F
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing operator/
technician which could result in death or serious injury,
and equipment or property-only damage. Test lift unit
approximately 24 inches (61 cm) to verify proper center
of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level.
WARNING
Risk of Unit Tipping!
Failure to do so may result in death or serious injury
should a lifting cable fail. Connect an anti-rotation strap
between the lifting beam and compressor before lifting
unit.
WARNING
Shipping Mounts!
Do not use the threaded holes in the compressor to lift
or assist in lifting the unit. They are not intended for
that purpose and could create a dangerous situation.
Do not remove the wood mounts until the unit is in its
final location. Removal of wood shipping mounts prior
to unit final locating could result in death or serious
injury or equipment damage.
NOTICE
Equipment Damage!
Never use a forklift to move the unit. The skid is not
designed to support the unit at any one point and
using a forklift to move the equipment may cause unit
damage. Always position the lifting beam so that
cables do not contact the unit. Failure to do so may
result in unit damage.
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...