Installation Electrical
48
RTHD-SVX01K-EN
Important:
•
For factory provided AFD units, verify jumper has
been removed.
•
For field installed drives, remove jumper shown in
.
AFD Drive Programming
Field replacement drives must be programmed via the
keypad interface. Program non-compressor specific
parameters first in sequential order (
), followed by
compressor specific parameters (see
) in
sequential order.
Figure 21.
AFD jumper
NOTICE
Equipment Damage!
Changing default clockwise phase rotation or enabling
phase reversal protection could prevent proper chiller
operation or cause equipment damage.
•
Do NOT change Adaptive Frequency™ drive (AFD)
phase rotation to counterclockwise.
•
Do NOT enable phase reversal protection.
Jumper between
terminals 12 and 37
must be removed
prior to unit
operation.
Table 16. Non-compressor specific parameter settings
ID
Description
Setting
0-03
Region Settings
North American
0-20
Display Line 1.1 Small
DC Link Voltage
0-22
Display Line 1.3
Heatsink Temp.
0-24
Display Line 3 Large
Analog Input 53
0-40
[Hand on] Key on LCP
Disabled
0-41
[Off] Key on LCP
Disabled
0-60
Main Menu Password
999
0-61
Access to Main Menu w/o Password
Read Only
1-03
Torque Characteristics
Compressor Torque
1-71
Start Delay
0s
1-73
Flying Start
Disabled
1-78
Compressor Start Max Speed [Hz]
20Hz
1-79
Compressor Start Max Time to Trip
10s
1-87
Trip Speed Low [Hz]
25Hz
3-02
Min Reference
30Hz
3-41
Ramp 1 Ramp up Time
10s
3-42
Ramp 1 Ramp Down Time
10s
3-82
Starting Ramp Up Time
5s
4-10
Motor Speed Direction
Clockwise
4-12
Motor Speed Low Limit [Hz]
30Hz
4-18
Current Limit
Max
5-02
Terminal 29 Mode
Output
5-12
Terminal 27 Digital Input
Coast Inverse
5-31
Terminal 29 Digital Output
Alarm
5-40
Function Relay 1
No Operation
6-10
Terminal 53 Low Voltage
2V
6-14
Terminal 53 Low Ref./Feedb. Value
30Hz
6-50
Terminal 42 Output
Power 4-20mA
14-00
Switching Pattern
SFAVM
14-03
Overmodulation
Off
14-10
Mains Failure
[4] Kinetic Back-Up
14-12
Function at Mains Imbalance
Derate
14-21
Automatic Restart Time
8s
14-50
RFI Filter
Off
14-51
DC Link Compensation
On
14-60
Function at Over Temperature
Derate
14-61
Function at Inverter Overload
Derate
14-62
Inv. Overload Derate Current
75%
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...