Diagnostics
RTHD-SVX01K-EN
81
Starter Module
Memory Error
Type 2
Chiller
Immediate Latch
All
Checksum on EEPROM copy of the Starter LLID
configuration failed. Factor default values used.
Local
Unexpected
Condenser
Water Flow
Heat
Recovery
Warning
NonLatch
Start and All Run
Modes
The main condenser water pump output was de-energize
for more than 180 contiguous seconds but the condenser
water flow proof input was closed(condenser water flow is
detected) . this diagnostic is automatically cleared once
the condenser water flow proof input was opened.
Remote
Unexpected Heat
Recovery Water
Flow
Heat
Recovery
Warning
NonLatch
Start and All Run
Mode
The heat recovery condenser water pump output was de-
energize for more than 180 contiguous seconds but the
condenser water flow proof input was closed(condenser
water flow is detected) . this diagnostic is automatically
cleared once the condenser water flow proof input was
opened.
Remote
Unexpected
Starter
Shutdown
Chiller
Normal
Nonlatch
All Cprsr Running
modes, Starting,
Running and
Preparing to
Shutdown
The Starter module status reported back that it is stopped
when it should be running and no Starter diagnostic exists.
This diagnostic will be logged in the active buffer and then
cleared.
NA
Table 26. Main processor diagnostics (continued)
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...