Start-Up and Shutdown
RTHD-SVX01K-EN
57
6. Check the adjustment and operation of each safety and
operating control.
7. Close all disconnect switches.
8. Refer to the sequence for daily unit startup for the
remainder of the seasonal startup
Sequence of Operation
This section will provide basic information on chiller
operation for common events. With microelectronic
controls, ladder diagrams cannot show today’s complex
logic, as the control functions are much more involved
than older pneumatic or solid state controls.
Adaptive control algorithms can also complicate the exact
sequence of operations. This section illustrates common
control sequences.
Software Operation Overview
The Software Operation Overview shown in
diagram of the five possible software states. This diagram
can be though of as a state chart, with the arrows and
arrow text depicting the transitions between states.
•
The text in the circles is the visible top level operating
mode displayed on Tracer™ AdaptiView.
•
The shading of each software state circle corresponds
to the shading on the time lines that show the state the
chiller is in.
There are five generic states that the software can be in:
•
Power Up
•
Stopped
•
Starting
•
Running
•
Stopping
•
Timelines
•
The time line indicates the upper level operating mode,
as it would be viewed on the Tracer AdaptiView™.
•
The shading color of the cylinder indicates the
software state.
•
Text in parentheses indicates sub-mode text as viewed
on Tracer AdaptiView™.
•
Text above the time line cylinder is used to illustrate
inputs to the Main Processor. This may include user
input to the Tracer AdaptiView™ Touch screen, control
inputs from sensors, or control inputs from a Generic
BAS.
Figure 24.
Software operation overview
Stopping
Preparing to Shut Down
Shutting Down
Running
Running
Running - Limit
Stopped
Stopped
Run Inhibit
RTHD Sequence Of
Operation Overview:
Auto
Auto
Waiting to Start
Starting Compressor
Sta
rt
Comm
and
Confirmed St
art
Stop Com
man
d
Diagnos
tic
Confir
me
d
Shutd
own
Power
Up
Fast Restart or Satisfied Setpoint
Stop Command or Diagnostic
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...