Diagnostics
80
RTHD-SVX01K-EN
Low Evaporator
Water Temp
(Unit Off)
Chiller
Warning
and Special
Action
NonLatch
Unit in Stop Mode,
or in Auto Mode and
No Ckt(s) Energized
[Any Ckt Energized]
The leaving Evaporator water temp. fell below the leaving
water temp cutout setting for 30 degree-F seconds while
the Chiller is in the Stop mode, or in Auto mode with no
compressors running. Energize Evap Water pump Relay
until diagnostic auto resets, then return to normal evap
pump control. Automatic reset occurs when the temp rises
2°F (1.1°C) above the cutout setting for 30 minutes.
Remote
Low Evaporator
Water Temp
(Unit On)
Chiller
Immediate
and Special
Action
NonLatch
Any Ckt[s]
Energized [No
Ckt(s) Energizd]
The Evaporator water temp. fell below the cutout setpoint
for 30 degree F Seconds while the compressor was
running. Automatic reset occurs when the temperature
rises 2 °F (1.1°C) above the cutout setting for 2 minutes.
This diagnostic shall not de-energize the Evaporator Water
Pump Output.
Remote
Low Oil Flow
Chiller
Immediate Latch
Chiller Energized
and Delta P above
15 Psid
The oil pressure was out of the acceptable pressure range
for 15 seconds, while the Delta Pressure was greater than
15 Psid.: Acceptable range is 0.50 or 0.60 > (PC-Po) / (PC-
PE) for the first 2.5 minutes of operation, and 0.40 or 0.50
> (PC-Po) / (PC-PE) thereafter. The higher ratios used if the
system DP is less than 23 psid
Local
Motor Winding
Temp Sensor
Chiller
Warning
Latch
All
Both of the motor winding temperature sensors are seen
to be out of their normal range. (Severity is adjustable via
TU Service Tool – default is Warning)
Local
MP: Invalid
Configuration
Platform Immediate Latch
All
MP has an invalid configuration based on the current
software installed
Remote
MP: Reset Has
Occurred
Chiller
Warning
NonLatch
All
The main processor has successfully come out of a reset
and built its application. A reset may have been due to a
power up, installing new software or configuration. This
diagnostic is immediately and automatically cleared and
thus can only be seen in the Historic Diagnostic List in
Tracer TU.
Remote
No Differential
Refrigerant
Pressure
Chiller
Immediate Latch
Chiller Energized
The system differential pressure was below 7.7 Psid. The
occurrence of this diagnostic will saturate the above “Low
Diff Rfgt Press” Integral and invoke the same “Compressor
Cool Down” op mode.
Remote
Oil Flow
Protection Fault
Chiller
Immediate Latch
Starter Contactor
Energized [all Stop
modes]
The Oil Pressure Transducer for this Chiller is reading a
pressure either above its Condenser Pressure by 15 Psia or
more, or below its Evaporator Pressure 10 Psia or more for
30 seconds continuously.
Local
Oil Pressure
Transducer
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Outdoor Air
Temperature
Sensor
Chiller
Warning
and Special
Action
Latch
All
Bad Sensor or LLID. This diagnostic will only occur if OA
sensor is configured. OA Chilled water reset will be
suspended if selected and Tracer OA unavailable.
Remote
Refrigerant
Monitor Input
Chiller
Warning
NonLatch
All–if installed
Open or Shorted input and the Rfgt Monitor is setup as
installed
Remote
Restart Inhibit
Chiller
Warning
NonLatch
All
The Restart Inhibit was invoked on a compressor. This
indicates excessive chiller cycling which should be
corrected.
Remote
Software Error
Number: 1001
Call Trane
Service
All
functions Immediate
Latch – power
down reset is
reqd
all
A high level software watchdog has detected a condition in
which there was a continuous 5 minute period of
compressor operation, with neither chilled water flow nor
a” contactor interrupt failure” diagnostic active. The
occurrence of this software error message suggests an
internal software state chart misalignment has occurred.
The events that led up to this failure, if known, should be
recorded and transmitted to Trane Controls Engineering –
(SW rev 6 and higher)
local
Starter Failed to
Arm/Start
Chiller
Warning
Latch
All
Starter failed to arm or start within the allotted time (2
minutes).
Remote
Starter Module
Memory Error
Type 1
Chiller
Warning
Latch
All
Checksum on RAM copy of the Starter LLID configuration
failed. Configuration recalled from EEPROM.
Local
Table 26. Main processor diagnostics (continued)
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
Содержание Optimus RTHD
Страница 27: ...Installation Mechanical RTHD SVX01K EN 27...
Страница 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Страница 29: ...Installation Mechanical RTHD SVX01K EN 29...
Страница 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Страница 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Страница 95: ...Notes RTAF SVX001K EN 95...